InteliGen
NT
, InteliSys
NT
, InteliMains
NT
– Troubleshooting Guide,
SW version IGS-NT-3.1.0, IM-NT-3.1.0, ©ComAp
– August 2018
35
IGS-NT Troubleshooting Guide.pdf
IGS-NT Alarm/History
record
Alarm/
History
Appeara
nce
Description
phase to neutral voltages. It means that
Basic settings
:
FixVoltProtSel
is set to PHASE-NEUTRAL.
BusL L1, L2 or L3 over
H
Left bus L1, L2 or L3 voltage was over the
BusLeft >V
limit
for the
BusLeft V del
time
.
Information about that is
recorded into controller history.
Setpoint
BusL protect
:
BusL Volt prot
has to be set to
ENABLED if healthy bus voltage detection and history
record are requested. Voltage has to be below the
BusLeft
>V
limit if BTB synchronisation should be started, because
the
BusLeft >V
setpoint is used for healthy bus detection
(this condition applies only if
BusL Volt prot
is set to
ENABLED).
This alarm is issued if voltage protections are based on
phase to neutral voltages. It means that
Basic settings
:
FixVoltProtSel
is set to PHASE-NEUTRAL.
BusL L12, L23 or L31 under
H
Left bus L12, L23 or L31 voltage was under the
BusLeft <V
limit for the
BusLeft V del
time
.
Information about that is
recorded into controller history.
Setpoint
BusL protect
:
BusL Volt prot
has to be set to
ENABLED if healthy bus voltage detection and history
record are requested. Voltage has to be over the
BusLeft
<V
limit if BTB synchronisation should be started, because
the
BusLeft <V
setpoint is used for healthy bus detection
(this condition applies only if
BusL Volt prot
is set to
ENABLED)..
This alarm is issued if voltage protections are based on
phase to phase voltages. It means that
Basic settings
:
FixVoltProtSel
is set to PHASE-PHASE.
BusL L12, L23 or L31 over
H
Left bus L12, L23 or L31 voltage was over the
BusLeft >V
limit for the
BusLeft V del
time
.
Information about that is
recorded into controller history.
Setpoint
BusL protect
:
BusL Volt prot
has to be set to
ENABLED if healthy bus voltage detection and history
record are requested. Voltage has to be below the
BusLeft
>V
limit if BTB synchronisation should be started, because
the
BusLeft >V
setpoint is used for healthy bus detection
(this condition applies only if
BusL Volt prot
is set to
ENABLED).
This alarm is issued if voltage protections are based on
phase to phase voltages. It means that
Basic settings
:
FixVoltProtSel
is set to PHASE-PHASE.
BusR L1, L2 or L3 under
H
Right bus L1,L2 or L3 voltage was under the
BusRight <V
limit for the
BusRight V del
time
.
Information about that is
recorded into controller history.
Setpoint
BusR protect
:
BusR Volt prot
has to be set to
ENABLED if healthy bus voltage detection and history
record are requested. Voltage has to be over the
BusRight
<V
limit if BTB synchronisation should be started, because
the
BusRight <V
setpoint is used for healthy bus detection
(this condition applies only if
BusR Volt prot
is set to
ENABLED).
This alarm is issued if voltage protections are based on
phase to neutral voltages. It means that
Basic settings
:
FixVoltProtSel
is set to PHASE-NEUTRAL.
BusR L1, L2 or L3 over
H
Right bus L1, L2 or L3 voltage was over the
BusRight >V