How to …
Special applications
Setup your controller to work as the SSB application
SSB application is known from IG/IS classic controllers, but it is no more present among NT
applications. So you have to modify behaviour of the SPtM application to achieve that. This type of
application can be handled with IL-NT AMF controllers.
Start with the default SPtM archive and set the following setpoints in the
ProcessControl
group of
setpoint:
•
Island enable
= YES (stand-by application needs to work in island when mains is gone)
•
ParallelEnable
= NO (no mains paralleling is allowed)
•
SynchroEnable
= NONE (no synchronizing is allowed)
•
MFStart enable
= YES (basic function of the SSB application
– start upon mains failure)
Setup your controller to work as the SPM application
SPM application is known from IG/IS classic controllers, but it is no more present among NT
applications. So you have to modify behaviour of the MINT application to achieve that. This type of
application can be handled with IL-NT MRS controllers.
Start with the default MINT archive and follow these instructions:
•
The controller with MINT, COX or Combi in MINT archive can work without Dongle LSM+PMS
if all following conditions are fulfilled
o
The power management must be disabled (Pwr management = DISABLED)
and
o
(SysLdCtrl PtM must be swithed to BASE LOAD and MCB feedback must be 1)
or
there
is no CAN2 communication
The conditions above allow user to use the following combinations without Dongle:
Pwr
management
SysLdCtrl PtM
MCB feedback
CAN2
communication
DISABLED
BASE LOAD
1
YES
DISABLED
ANY
ANY
NO
If the above conditions are fulfilled, there is no
“Dongle incomp” message displayed in
controller Alarm list. This message is normally displayed by controller with MINT application as
the IGS-NT-LSM+PMS dongle is expected to be used for standard use of the MINT
application. In this special case and providing the stated conditions, the message is
suppressed to allow controller to work in the SPM mode.