InteliGen
NT
, InteliSys
NT
, InteliMains
NT
– Troubleshooting Guide,
SW version IGS-NT-3.1.0, IM-NT-3.1.0, ©ComAp
– August 2018
43
IGS-NT Troubleshooting Guide.pdf
IGS-NT Alarm/History
record
Alarm/
History
Appeara
nce
Description
Setpoints
Sync/Load ctrl
:
GCB open level
and
GCB open
del
are related to genset unloading too.
Cooling
H
Engine is cooling down
Emerg man
H
Emerg. manual binary input function is active
Not ready
H
Genset is not ready to start. Controller is either in OFF
mode or any 2
nd
level alarm is in controller alarm list.
ExcitationON/ ExcitationOFF
H
It indicates activation/deactivation of excitation in case of
configuration the SUS sequence function.
Wrn SUSminPwr
A+H
It indicates that require power from the gen-sets with
activated LBO:ReadyToExcite was not achieved (require
power is set by setpoint #SUS min power).
SUS seq blck
A
Alarm indicates that SUS sequence is required, but
setpoint Gear teeth is equal 0. (SUS sequence require
pick-up sensor for correct function).
SUSseq break-1
H
MCB is closed (in SPTM application).
SUSseq break-2
H
MCB is open (MCB feedback is not active) OR Mains
voltage is higher than 1/3 of setpoint Basic
settings:MainsNomV
(in SPI application).
SUSseq break-3
H
Bus voltage is higher than 1/3 of setpoint Basic
settings:BusNomV (in MINT application).
SUSseq break-4
H
GCB was not closed during the Prestart Time count down.
SUSseq break-5
H
Setpoint SUS control:ExcitationCtrl=EXTERNAL. The LBI:
SUSexcitBlck was not activated before engine start OR it
was deactivated before the LBO: ReadyToExcite activation
1
This alarm may be displayed as Wrn or Sd alarm type. Alarm type depends on
Protection upon
module failure
setting in Modules card in GenConfig. Available settings are: No Protection,
Warning and Shutdown.
2
See setting of Force Protect functions on the PLC card in GenConfig to find out what PLC State x
texts were changed to.
3
Hold Enter and push Esc to enter the
Info screen 1. Push the right arrow → to enter Info screen 2
to read IDch and Dngl strings or controller serial number and Password Decode number
(Pwd.Dec.).
4
You can exchange battery by yourself, but
ComAp would not be responsible for controller
damage caused by battery exchange then.
See our
AS08
– Battery exchange process r1
manual for instructions, if you would like to exchange controller battery by yourself.
5
See Al./Hist. msg column on Protections card in GenConfig to see customized alarm messages
which are related to configurable protections.
6
Speed control related regulation loops are part of the
Sync/Load ctrl
group of setpoints:
Frequency regulation loop:
Freq gain, Freq int
setpoints
Angle regulation loop:
Angle gain
setpoint
Load regulation loop:
Load ramp, Load gain, Load int
setpoints
Load sharing loop:
LS gain, LS int
setpoints
7
Voltage control related regulation loops are part of the
Volt/PF ctrl
group of setpoints:
Voltage regulation loop:
Voltage gain, Voltage int
setpoints
Power Factor regulation loop:
PF gain, PF int
setpoints
VAr sharing regulation loop:
VS gain, VS int
setpoints
8
Alarm is related to Generator voltage terminals connection
9
Alarm is related to Mains (Bus) voltage terminals connection
10
In GenConfig go to File - Generate Cfg Image - Generate Cfg Image (Comm.objects) to obtain the
communication objects list
11
In InteliMonitor go to Monitor - Admin Users to do any user administration changes