InteliLite
NT
– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 30
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
Inputs and Outputs
For Inputs/Outputs overview table see chapter Technical Data.
Not used
Binary input has no function. Use this configuration when binary input is not connected.
Alarm
If the input is closed (or opened) selected alarm is activated.
Binary Alarm configuration items
Name
14 characters ASCII string
NC Normally
closed
Contact type
NO Normally
opened
Warning
Alarm type
Shut down
All the time
Valid if checkbox “Engine running
only” is not checked
Alarm active
Engine running only
Valid if checkbox “Engine running
only” is checked
Control
Use this setting to configure the desired function from the list below.
Hint:
In 1.2 version of FW, there is a possibility to function without feedback from GCB and MCB.
Binary Inputs – List
Rem Start/Stop
External request for engine run. AUT mode only.