Analog inputs
Two analog inputs are available on the IL-NT.
Configuration
Each analog input can be configured by LiteEdit software following way.
Analog input item
LiteEdit
Possibility
Type Type
Not
used
Alarm
Analog input isn’t used
Analog input name
Name
Up to 14 ASCII characters
Config of input
Config
Analog
Binary (not supp. by PTM)
Tri-state (not supp. by PTM)
ECU
Analog measuring in specified
range.
Binary: open/close - threshold
750
Ω
.
Three-state: open/close -
threshold 750
Ω
,
Failure <10
Ω
or > 2400
Ω
Value is read from ECU
Physical dimension
Dim
bar,%,°C, …
Up to 4 ASCII characters
(Valid only for analog inputs)
Polarity Contact
type
NC
NO
Valid only for binary and three-
state inputs
Valid only for binary and three-
state inputs
Over
Overstep. Sensor Fail does
not activate protection.
Over+Fls
Overstep and Sensor Fail
activates protection.
Under
Under step. Sensor Fail does
not activate protection.
Protection direction
Protection
Under+Fls
Under step and Sensor Fail
activates protection.
Sensor characteristic Sensor Predefined
user
curves
User changeable and
configurable
Resolution
Resolution
0 – 0,00001
Sensor resolution
(Valid only for analog inputs)
User Curves are adjustable in LiteEdit.
Each Analog input has separate set points for two level alarm setting. Analog input alarm levels and
delay adjust in
Basic settings
group.