– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 33
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
Analog Inputs
It is possible to configure on each Analog input:
•
Reading from IL Analog inputs or from Engine Control Unit via CAN bus (J1939)
•
Sensor characteristics – from the list, or custom sensor curve
•
Value dimension (e.g. psi - bars,
°
F -
°
C, % - l)
•
Sensor resolution
Warning and shut-down limits are adjusted in
Engine protect
group.
The analog inputs are configurable. Use LiteEdit software to modify configuration. Default
configuration is:
Oil Pressure
Oil pressure analog input. Default range 0 to 10.0 bars.
Engine Temp
Water temperature analog input. Default range 40 to 120
°
C.
Analog Outputs
Optional plug in card IL-NT AOUT8 provides eight Pulse-With-Modulation (PWM) outputs. These are
intended to drive VDO style analog gauges. This is to provide visual indication of typically ECU values
without installing aditional sensors on the engine. PWM signal emulates sensor which would be
typically mounted on the engine.
Any value from controler may be configured to the outputs. Use LiteEdit PC SW to configure
corresponding sensor/gauge curve and value selection.