InteliLite
NT
– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 34
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
Setpoints
Password
EnterPassword
Password is a four-digit number. Password enables change of specificaly marked protected setpoints.
Use
↑
or
↓
keys to set and ENTER key to enter the password.
Hint:
There is only 1 level of a password.
ChangePassword
Use
↑
or
↓
keys to set and ENTER key to change the password.
Hint:
At first the Password has to be entered before the new Password can be changed.
Basic Settings
Gen-set Name
User defined name, used for InteliLite identification at remote phone or mobile connection.
Gen-set name
is max 14 characters long and have to be entered using LiteEdit software.
CT Ratio
[/5A]
Gen-set phases current transformers ratio.
Step:
1 A
Range:
1 – 5000 A / 5A
Hint:
For CT Ratio <= 250 the values of power and current are displayed in a controller with one tenth. For
CT Ratio > 250 the values of power and current are displayed in a controller with integers. If you
change CT Ratio in LiteEdit or directly in the controller, decimal numbers will not be changed
immediately. The change will be executed only by reconfiguring in LiteEdit. The statistics of power will
be recounted at this time with regards to decimal numbers of power.
WARNING!
When you change the firmware, statistics can be invalid!
Nominal Freq
[Hz]
Nominal generator frequency (usually 50 or 60 Hz )
Step:
1Hz
Range:
45 – 65 Hz
Prestart
Time
[s]
Time of closing of the PRE-START output prior to the engine start.
Set to zero if you want to leave the output PRE-START open.
Step:
1s
Range:
0 – 600 s