ECON-4 1.4.0 Global Guide
51
Setpoint group
Engine RPM
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
1 - 20 [%]
Default value
8 %
Force value
NO
Step
1 %
Comm object
7193
Related applications
ALL
Setpoint visibility
Always
Description
Percentage Change of Requested RPM from Nominal RPM. This setpoint defines the maximum allowable
change of requested RPM from the Nominal RPM value in case the BIN or ANA control of RPM is used.
Use this setpoint to enlarge maximum allowable swing of the required RPM. Setpoint is by default adjusted
to 8% which should fulfill the most of installations.
PerChSpdNom
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4
ADV extension module
Range [units]
IDLE FUEL – CLOSE
Default value
-
Force value
NO
Step
-
Comm object
14409
Related applications
ALL
Setpoint visibility
WinScope only
Description
Value set to output GAS Dose when RPM reaches value in setpoint PreOverSpeed.
PreOverSpReduct
8.1.4 Group: Engine StartGroup: ECON4-EngStart
Setpoint group
Engine RPM
Related FW
1.4.0
Range [units]
Start RPM - Nominal RPM
Default value
10%
Force value
NO
Step
1 %
Comm object
7172
Related applications
ALL
Setpoint visibility
Always
Description
Initial position of the actuator during start
InitStart dose