ECON-4 1.4.0 Global Guide
29
BI14
ActFdbErr
Active actuator feedback error
BI15
ActOverldProt
Active overload protection
BI16
InvalSetpoints
Setpoints CRC fail
5.3.2 Data Binary outputs
ECON-4 accepts the data from InteliSys-NT (specific sw branches only) instead from Physical Binary inputs,
when setpoint
Engine RPM
: Speed request = DATA.
ECON-4
Name
BO1
MCB feedback
BO2
GCB feedback
BO3
Nominal
BO4
Run/Stop Â
BO5
Droop
The physical RUN/STOP – S5.6 binary input must be closed in any type of control to run ECON-4 i.e. in “DATA
mode” together with data command BO4 Run/Stop to enable speed control function (unblock the actuator from
0% position).
5.3.3 Data Analog inputs
ECON-4
Name
Logical function
AI1
Engine RPM
RPM pick-up;
(RPM value source for IS-NT)
AI2
Misfiring Amplitude
1
No RPM pickup is needed in IS-NT. Configure IS-NT – I /O – ECON-4– AIN1 Engine RPM for
Function = RPM pick-up
Sensor = Electronic
5.3.4 Data Analog outputs
ECON-4
Name
Function
AOUT1
Active power - relative
0,0 - 100,0 % (option)
AOUT2
SpeedReq RPM
In RPM /8 (option)
Active power value is required for Load anticipation function – see Main PID: Load anticip. In GenConfig choose
value: Gener values: Act Pwr rel, option Normalize – YES, resolution 0,1.
For AOUT2 choose: Sync/Load ctrl: SpeedReqRPM and leave the default settings of this output.
5.3.5 ECON adjustement for various types of actuators
Basically there are available 3 types of actuator types:
LINEAR
– actuator is driven by a current, which acts against a spring which pushes the actuator to close
position. Actuator is equipped with position feedback signal. Available feedback signal for ECON is 0,4 to
4,6 Volts DC.
1
Misfiring evaluation from ECON-4 is not implemented in version 1.0