ECON-4 1.4.0 Global Guide
74
Setpoint group
Analog sensors
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
Fdb1 0 pos – 4,60 V
Default value
3.10
Force value
NO
Step
0.01 V
Comm object
11664
Related applications
ALL
Setpoint visibility
WinScope only
Description
Feedback fully opened position voltage. Connect the position feedback to the ECON-4 terminals. Keep the
actuator lever in fully opened position (by hand) and measure a dc voltage between the terminals S2.1 and
S2.3. This voltage put as this setpoint value.
FBD 100 pos
8.1.11 List of tested actuators by ComAp
Woodward ITB 0-200mA
Woodward ITB PWM
Woodward F-series PWM
Act gain = 5
Act gain = 20
Act gain = 0,5
Act int = 100
Act int = 400
Act int = 200
Act der = 0
Act der = 0
Act der = 0
PWM rate = 2000 Hz
PWM rate = 2000 Hz
PWM rate = 2000 Hz
Fdb 0 pos = 0,5 V
Fdb 0 pos = 0,5 V
Fdb 0 pos = 0,42 V
Fdb 100 pos = 4,5 V
Fdb 100 pos = 4,5 V
Fdb 100 pos = 4,55 V
Heinzmann STG10
Heinzmann STG30
Heinzmann STG2040
Act gain = 90
Act gain = 90
Act gain = 35
Act int = 600
Act int = 600
Act int = 300
Act der = 150
Act der = 150
Act der = 150
PWM rate = 6000 Hz
PWM rate = 6000 Hz
PWM rate = 6000 Hz
Fdb 0 pos = 1,76 V
Fdb 0 pos = 1,76 V
Fdb 0 pos = 1,78 V
Fdb 100 pos = 3,1 V
Fdb 100 pos = 3,1 V
Fdb 100 pos = 2,8 V
Heinzmann STG2010
GAC ATB552t2F-24
Act gain = 30 (40)
Act gain = 25
Act int = 300 (500)
Act int = 400
Act der = 30 (300)
Act der = 2
PWM rate = 6000 Hz
PWM rate = 2000 Hz (1500 - 3000???)
Fdb 0 pos = 1,78 V
Fdb 0 pos = 0,96 V
Fdb 100 pos = 2,8 V
Fdb 100 pos = 3,61 V