ECON-4 1.4.0 Global Guide
46
8.1.3 Group: Engine StartGroup: ECON4-EngRPM
Setpoint group
Engine RPM
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
Start RPM - Nominal RPM
Default value
1000 RPM
Force value
NO
Step
1 RPM
Comm object
7186
Related applications
ALL
Description
Engine idle speed.
Idle RPM
Setpoint group
Engine RPM
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0 - 2500 [RPM]
Default value
1500 RPM
Force value
NO
Step
1 RPM
Comm object
7187
Related applications
ALL
Setpoint visibility
Always
Description
Nominal engine speed.
Nominal RPM
Setpoint group
Engine RPM
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0 - 2500 [RPM]
Default value
1800 RPM
Force value
NO
Step
1 RPM
Comm object
7168
Related applications
ALL
Setpoint visibility
Always
Description
Maximum acceptable speed of the engine. If the actual engine speed is higher, ECON-4 immediately closes
the actuator. Normal function is restored after detection of zero engine speed.
Overspeed