MODULAR CONFIGURATION UNITS
Set the correct date and time on each unit before connecting
them to the network.
Set multiple configuration on each unit.
SW12-2 :
ON unit on modular configuration (or enabling DHW menu)
OFF single unit
The modular configuration is made up of two networks: the
controller network and the unit network (main keypads).
Each network can have max 16 addresses (0 to 15) and must be
addressed separately.
Each network has its own master, which must have address = 0.
If some of the slave units do not have the DHW option:
configure a unit without a DHW option as the master.
assign the higher addresses to the slave units equipped with
DHW option
Unit addressing
Addressing is carried out through encoder ENC4 on the back of
the keypad.
The address corresponds to the number on the encoder
The address is shown on the display DSP1.
E.g.:
MASTER : address = 0 encoder = 0
SLAVE 1 : address = 1 encoder = 1
SLAVE 15 : address = 15 encoder = F
The address of the unit is shown on display “DSP1” on the main
keypad.
Addressing controls
A maximum of 16 controls can be addressed, with address from
0 to 15; so for example :
16 units with relative controller on board, il master con
indirizzo 0, gli slave, the master with address 0, the slave, in
read-only mode, with subsequent ones
15 units with relative controller on board + a remote
controller as the master
Press MENU +
for 3 seconds
Press
to select the address
Remote ON-OFF
With the units in modular configuration, remote control must be
applied to the master unit, which transmits it to the slave units.
Modular unit communication bus
14 MODULAR CONFIGURATION UNITS