TW probe
The total system supply water control probe is installed on the supply pipe in the fan compartment.
With the unit in modular configuration, the master unit’s TW probe must be reinstalled on the system’s
common supply line, as far away as possible.
Use the additional probe trap in the electrical panel.
Keep the connection to the electrical panel, just remove the sensor that is inserted in the water supply pipe
inside the trap. The probe is physically clamped by a cable gland.
Taf1 Probe
The domestic hot water antifreeze protection probe is located inside the electrical panel in a plastic bag
with a 10m long cable.
To remotely control the Taf1 probe, electrically disconnect the one in the electrical panel (only 3 m long)
and connect the one in the bag labelled Taf1 to the same connector.
T5 Probe
The temperature probe that switches from system to domestic hot water is located inside the electrical
panel in a plastic bag with a 10m long cable. Connect it to the free connector labelled “T5” in the electrical
panel..
Keypad remote connections
The keypad is wired on the unit.
It can be disassembled and installed remotely.
Maximum distance 40 m.
Power supplied by the unit.
Maximum distance 300 m.
Separate power supply
Power supply provided with the
unit.
6 - ELECTRICAL CONNECTIONS