Power supply cables section
Signals / data lines
Do not overpass the maximum power allowed, which varies, according to the type of signal.
Lay the cables far from power cables or cables having a different tension and that are able to emit
electromagnetic disturbances.
Do not lay the cable near devices which can generate electromagnetic interferences.
Do not lay the cables parallel to other cables; cable crossings are possible, only if laid at 90°.
In case of parallel power supply and signal cables, use separate metal ducts. Minimum distance between
power supply and signal cables:
300 mm for absorption up to 10A.
500 mm for absorption up to 50A.
Connect the screen to the ground, only if there aren’t disturbances.
Guarantee the continuity of the screen during the entire extension of the cable.
Respect impendency, capacity and attenuation indications.
10.1 - 14.1
16.2 - 22.2
30.2 - 40.2
Max. cable section Cu (mm²)
16
25
25
Power supply network requirements
1 The short circuit capacity of the line must be less than 15 kA
2 The units can only be connected to TN, TT distribution systems
3 Voltage 400-3-50 +/-10%
4 Phase unbalance < 2%
5 Harmonic distortion less than 12% (THDv<12%)
6 Voltage interruptions lasting no longer than 3ms and with at least 1 s between each one
7 Voltage dips not exceeding 20% of the RMS value, lasting no longer than a single period (50Hz) and
with at least 1 s between each dip.
8 Earth cable as specified in the table:
Cross-section of the line conductors
(mm
2
)
Minimum cross-section of the protective conductor
(PE) (mm
2
)
S
≤
16
S
16 < S
≤
35
16
S > 35
S/2
6 - ELECTRICAL CONNECTIONS
EMC filter
Option available for installation in residential, commercial and light industrial environments for
conducted emissions (direct connection to the public grid).
It allows the unit to be installed in residential, commercial or light industrial environments, reducing electromagnetic
interference.