42
press
only if the ALARM symbol is flashing
ee
type of alarm (see table)
0
generic alarm (1 circuit1 alarm,
etc.)
030
progressive alarm number
press
7
days since the alarm was
triggered
17:00 alarm
time
previous menu
scroll the alarms
exit without alarms RESET
exit with alarms RESET:
scroll and select RES
To visualize alarm in progress
Caution
Before resetting an alarm identify and remove its cause.
Repeated resets can cause irreversible damage.
Type of alarm
Code Type
Restore
ee
Electric Automatic
eE
Electric
From Auto to manual*
EE
Electric Manual
ii
Idraulic Automatic
iI
Idraulic
From Auto to manual*
II
Idraulic Manual
ff
Refrigerator
Automatic
fF
Refrigerator
From Auto to manual*
FF
Refrigerator
Manual
aa
Aeraulic Automatic
aA
Aeraulica
From Auto to manual*
AA
Aeraulica Manual
* After "n" times the alarm has been triggered, it is
necessary to conduct a manual reset.
16.3 C°
17:00
ee
0030
007
17:00
ee
0030
ee
0030
RES
The code of the circuit 2 alarms is
2nn
:
example:
fF
113
:DI High pressure = circuit
1
fF
213
:DI High pressure = circuit
2
Содержание CSRN-XHE2 Series
Страница 1: ...CSRN XHE2 49 4 110 4 R 410A M07V40B13 07 11 20 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Страница 75: ...Dimensional drawings 75...
Страница 77: ...Dimensional drawings 77...
Страница 79: ...Dimensional drawings 79...
Страница 81: ...Dimensional drawings 81...
Страница 83: ...Dimensional drawings 83...
Страница 85: ...Dimensional drawings 85...
Страница 87: ...Dimensional drawings 87...
Страница 89: ...Dimensional drawings 89...
Страница 91: ...Dimensional drawings 91...