FAS-FHS-072-180-01SI Rev. A

1-22

Installation, Start-up and 

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS  . . . . . . . . . . . . . . . 1

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . 2

Moving and Storage  . . . . . . . . . . . . . . . . . . . . . . 2

Rigging   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSTALLATION  . . . . . . . . . . . . . . . . . . . . . . . . . . 2

General   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Uncrating  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . 12

Unit Positioning   . . . . . . . . . . . . . . . . . . . . . . . . 12

Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . 13

Refrigerant Piping Access . . . . . . . . . . . . . . . . 13

Condensate Drain  . . . . . . . . . . . . . . . . . . . . . . . 17

Fan Motors and Drives  . . . . . . . . . . . . . . . . . . . 17

Power Supply and Wiring   . . . . . . . . . . . . . . . . 17

Connecting Ductwork . . . . . . . . . . . . . . . . . . . . 22

• DISCHARGE CONNECTIONS

• RETURN CONNECTIONS

• OUTDOOR-AIR INLET CONNECTIONS

Return-Air Filters   . . . . . . . . . . . . . . . . . . . . . . . 22

START-UP  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Adjusting TXV for Superheat . . . . . . . . . . . . . . 24

SERVICE  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Panels   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Fan Motor Lubrication  . . . . . . . . . . . . . . . . . . . 24

Fan Shaft Bearings  . . . . . . . . . . . . . . . . . . . . . . 24

Centering Fan Wheel   . . . . . . . . . . . . . . . . . . . . 25

Fan Shaft Position Adjustment  . . . . . . . . . . . . 25

Individual Fan Wheel Adjustment  . . . . . . . . . . 25

Fan Belts  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Fan Rotation  . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Fan Pulley Alignment  . . . . . . . . . . . . . . . . . . . . 26

Pulley and Drive Adjustment  . . . . . . . . . . . . . . 26

Condensate Drains  . . . . . . . . . . . . . . . . . . . . . . 26

Return-Air Filters   . . . . . . . . . . . . . . . . . . . . . . . 26

Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Cleaning Cooling Coil   . . . . . . . . . . . . . . . . . . . 26

Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . 26

Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . 37

START-UP CHECKLIST . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can

be  hazardous  due  to  system  pressure  and  electrical

components. Only trained and qualified service personnel

should install, repair, or service air-conditioning equipment.

Untrained  personnel  can  perform  basic  maintenance

functions of cleaning coils and filters and replacing filters. All

other  operations  should  be  performed  by  trained  service

personnel.  When  working  on  air-conditioning  equipment,

observe  precautions  in  the  literature,  tags  and  labels

attached to the unit, and other safety precautions that may

apply.

Follow all safety codes, including ANSI (American National

Standards Institute) Z223.1. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations. Have

fire extinguisher available for all brazing operations.

It  is important to recognize  safety information. This  is the

safety-alert symbol 

. When you see this symbol on the

unit and in instructions or manuals, be alert to the potential

for personal injury.

Understand  the  signal  words  DANGER,  WARNING,

CAUTION,  and  NOTE.  These  words  are  used  with  the

safety-alert  symbol.  DANGER  identifies  the  most  serious

hazards which 

will

 result in severe personal injury or death.

WARNING signifies hazards which 

could

 result in personal

injury  or  death.  CAUTION  is  used  to  identify  unsafe

practices,  which 

may

  result  in  minor  personal  injury  or

product and  property damage.  NOTE  is used  to highlight

suggestions  which 

will

  result  in  enhanced  installation,

reliability, or operation.

DANGER

ELECTRICAL SHOCK HAZARD

Failure to follow this warning will result in personal injury

or death.

Before  performing  service  or  maintenance  operations

on unit, turn  off main  power switch to  unit and install

lock(s) and lockout tag(s). Ensure electrical service to

rooftop unit agrees with voltage and amperage listed on

the  unit  rating  plate.  Unit  may  have  more  than  one

power switch.

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure  to  follow  this  warning  could  cause  personal

injury, death and/or equipment damage.

R-410A refrigerant systems operate at higher pressures

than standard R-22 systems. Do not use R-22 service

equipment  or  components  on  R-410A  refrigerant

equipment.

FAS/FHS 072-180

Packaged Air-Handling Units

with R-410A Refrigerant

Содержание FAS072

Страница 1: ...nit and other safety precautions that may apply Follow all safety codes including ANSI American National Standards Institute Z223 1 Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire extinguisher available for all brazing operations It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in ins...

Страница 2: ...th electric heat accessory Front 2 1 2 ft 762 mm Right Side 3 1 2 ft 1067 mm Left Side 2 1 2 ft 762 mm For units equipped with an economizer refer to the accessory installation instructions for additional clearance requirements Be sure floor wall or ceiling can support unit weight Tables 1 4 See Fig 2 and 3 for dimensions Uncrating Move unit as near as possible to final location before remov ing s...

Страница 3: ...fficiency Motor High Drive FAS 6 to 15 ton 208 230V 460v 6 to 10 ton 575v 3 60 1 speed all 2 speed E High Static High Efficiency Motor High Drive FAS 15 ton all 3 phase F R 410A Fan Coil Unit A Air Conditioning Cooling Only H Heat Pump S Standard Efficiency Nominal Tonnage Future Use Fan Speed Controller F A S 0 9 1 M A A A 0 A 0 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 FHS 12 5 and 15 ton only High Alt...

Страница 4: ...4 Specifications subject to change without notice FAS FHS 072 180 01SI Rev A Fig 2 Dimensions Sizes 072 120 ...

Страница 5: ...FAS FHS 072 180 01SI Rev A Specifications subject to change without notice 5 Fig 2 Dimensions Sizes 072 120 cont ...

Страница 6: ...6 Specifications subject to change without notice FAS FHS 072 180 01SI Rev A Fig 3 Dimensions Size 150 and 180 ...

Страница 7: ...FAS FHS 072 180 01SI Rev A Specifications subject to change without notice 7 Fig 3 Dimensions Size 150 and 180 cont ...

Страница 8: ...2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Face 50 50 Face 50 50 Rows Fins in 4 15 4 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 2 1 1 8 DX Coil Liquid Refrigerant ODF 1 5 8 1 5 8 2 5 8 2 5 8 2 5 8 Steam Coil In MPT 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Steam Coil Out MPT 1 1 1 2 1 1 1 2 1 1 1 2 1 1 ...

Страница 9: ... 64 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Face 50 50 Face 50 50 Rows Fins m 4 591 4 591 4 591 4 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 2 1 1 8 DX Coil Liquid Refrigerant ODF 1 5 8 1 5 8 2 5 8 2 5 8 2 5 8 Steam Coil In MPT 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Steam Coil Out MPT 1 1...

Страница 10: ... of Splits 1 1 1 2 2 No of Circuits per Split 15 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 DX Coil Liquid Refrigerant ODF 1 5 8 1 5 8 1 5 8 2 5 8 2 5 8 Steam Coil In MPT 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Steam Coil Out MPT 1 1 1 2 1 1 1 2 1 1 1 2 ...

Страница 11: ... 1 2 2 No of Circuits per Split 15 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins m 3 591 4 591 4 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 DX Coil Liquid Refrigerant ODF 1 5 8 1 5 8 1 5 8 2 5 8 2 5 8 Steam Coil In MPT 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Steam Coil Out MPT 1 1 1 2 1 1 1 2 1 1 1 2 1 1 1 2 1 ...

Страница 12: ...n air location Refer to overhead suspension accessory drawing see Fig 6 for preferred suspension technique The unit needs support underneath to prevent sagging Unit Isolation Where extremely quiet operation is essential install isola tors between floor and base of unit or between ceiling and top section of unit Be sure that unit is level and adequately supported Use channels at front and sides of ...

Страница 13: ...ient access to the unit s coils for all FAS072 091 120 150 and 180 and FHS072 091 and 120 units FHS180 units require additional holes that must be field fabricated to accommodate the piping See Fig 7 for the positions and dimensions of the additional access holes re quired for RHS180 units Recommended access hole use is also listed for all units Note that Fig 7 shows the access holes on the contro...

Страница 14: ... 1 BBIZE 5 GA 1 1135 12 1 4 1 G4 FHS072 3 Row 1 BBIZE 5 GA 1 1136 15 1 4 1 G5 FHS072 2 4 Row 1 BBIZE 8 GA 1 1113 12 3 16 1 G5 FAS091 4 Row 1 BBIZE 6 GA 1 1136 15 1 4 1 G5 FHS091 4 Row 1 BBIZE 8 GA 1 1113 12 3 16 1 G5 FAS120 4 Row 2 BBIZE 4 GA 2 1135 9 1 4 2 G3 FHS120 4 Row 2 BBIZE 5 GA 2 1113 9 3 16 2 G3 FAS150 4 Row 2 BBIZE 5 GA 2 1113 12 3 16 2 G3 FAS180 4 Row 2 BBIZE 6 GA 2 1136 16 3 16 2 G4 FH...

Страница 15: ...5 1 2 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Street Elbow 5 8 Nipple 10 1 2 L 5 8 Long Radius Elbow 4 Suction Upper 1 1 8 Nipple 5 5 8 L 1 1 8 Long Radius Elbow 1 1 8 Nipple 12 L 1 1 8 Long Radius Elbow FAS150 1 Suction Lower 1 1 8 Street Elbow 1 1 8 Nipple 7 5 8 L 1 1 8 Long Radius Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 1 7 16 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Street Elbow ...

Страница 16: ...IAMS MIN 10 DIAMS 8 DIAMS MIN TXV SENSING BULB EQUALIZER LINE SIGHT GLASS TXV SOLENOID VALVE FILTER DRIER TXV SENSING BULB TXV 8 DIAMS MIN 15 DIAMS MIN 10 DIAMS INDOOR COIL EQUALIZER LINE Single Circuit Coil Piping Configuration FAS FHS 072 091 For single compressor condensing units Dual Circuit Coil Piping Configuration FAS FHS 120 180 For single compressor condensing units UPPER SPLIT AIRFLOW 15...

Страница 17: ...tch of at least 1 4 in over its length toward the drain connection Fig 11 Condensate Drain Fig 12 Drain Pan Slope Adjustment Fan Motors and Drives Motor and drive packages are factory installed in all units The motor and drive packages consist of the following items 1 fan motor 1 adjustable motor pulley 1 fan pulley 1 fan belt FAS072 120 FHS072 120 units 2 matched fan belts FAS150 180 FHS180 units...

Страница 18: ...414 506 2 4 1 79 2 6 4 0 15 575 3 60 518 632 2 0 1 49 2 4 3 0 15 FAS150 208 230 3 60 187 253 2 9 2 16 7 5 10 0 15 460 3 60 414 506 2 9 2 16 3 4 5 0 15 575 3 60 518 632 3 0 2 24 3 8 5 0 15 FAS180 FHS180 208 230 3 60 187 253 3 7 2 76 10 2 13 0 20 460 3 60 414 506 3 7 2 76 4 8 6 0 15 575 3 60 518 632 3 0 2 24 3 8 5 0 15 Table 11 Electrical Data Alternate Motors Single Speed UNIT V PH Hz VOLTAGE LIMIT...

Страница 19: ...230 3 60 187 253 3 7 2 76 10 8 14 0 20 460 3 60 414 506 3 7 2 76 4 9 7 0 15 575 3 60 518 632 3 7 2 76 4 5 6 0 15 Table 13 Electrical Data Alternate Motors Two Speed UNIT V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA MINIMUM CIRCUIT AMPS MAX FUSE FAS072 FHS072 208 230 3 60 187 253 3 7 2 76 10 8 14 0 20 460 3 60 414 506 3 7 2 76 4 9 7 0 15 575 3 60 518 632 3 7 2 76 4 5 6 0 15 FAS091 FHS091...

Страница 20: ...ion with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the FAS FHS indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclosure and FAS FHS power entry location Install wires in field installed conduit Example Supply voltage is 230 3 60 Determine maximum deviation from average voltage AB 397 393 4 v BC 403 397 6 v AC 397 3...

Страница 21: ...ation replacing the 460 v sticker information on the units corner post Fan motors are factory installed on all units Indoor fan contactors are located in the fan contactor box behind the side access panel See Fig 14 and 15 Wire the thermo stat to the 24 v control circuit terminal block located in the side of the fan contactor control box according to Fig 16 or the unit label diagram If the air han...

Страница 22: ...ir ductwork route return air duct to the unit s return air inlet near the filter rack using a canvas connection to prevent transmission of unit vibration If the duct blocks off the unit s access panel provide a slip joint in the ductwork to permit removal for servicing OUTDOOR AIR INLET CONNECTIONS Connect outdoor air inlet to field installed accessory econo mizer Refer to Economizer Installation ...

Страница 23: ...FAS FHS 072 180 01SI Rev A Specifications subject to change without notice 23 Fig 17 Typical Fan Discharge Connections for Multiple Fan Units Fig 18 Duct Flange Installation ...

Страница 24: ...s orientation When service is completed replace unit panels Panels Panels are fastened to unit frame with sheet metal screws Fan and coil compartment must be sealed tightly after service to prevent air from bypassing the cooling coil Fan Motor Lubrication Fan motor supplied with unit is permanently lubricated and requires no further lubrication Fan Shaft Bearings Size 072 120 units are sealed perm...

Страница 25: ...2 Fan Shaft Bearing Individual Fan Wheel Adjustment Loosen the 2 locking bolts holding the fan wheel hub to shaft See Fig 21 Position fan wheel in center of the fan housing and tighten locking bolts Clearance between wheel and housing should be the same on both sides Fan Belts Motor mounting plate and motor support angles are slotted to permit both vertical and horizontal adjustment Adjust belt s ...

Страница 26: ...See Fig 25 Condensate Drains Keep condensate drains free of dirt and foreign matter Return Air Filters Refer to Replacing Filters section on page 37 for filter accessibility and removal Replace with clean filters of the sizes listed in Tables 1 4 Coil Removal Remove unit panels and corner posts as required Disconnect coil connections and remove fastening screws Remove coil through end or side sect...

Страница 27: ... 8 7 8 7 8 7 8 7 8 NEMA National Electrical Manufacturers Association Table 17 Fan Motor Data FAS FHS Alternate Motor Single Speed English UNIT FAS FHS 072 FAS FHS 091 FAS FHS 120 FAS 150 FAS FHS 180 208 230 1 60 Speed rpm 1725 1725 Hp 2 4 2 4 Frame NEMA 56Y 56Y Shaft Dia in 5 8 5 8 230 3 60 and 460 3 60S Speed rpm 1750 1750 1750 1750 1755 Hp 2 9 2 9 3 7 3 7 5 0 Frame NEMA 56Y 56Y 56HZ 56HZ 184T S...

Страница 28: ... 1 49 1 49 2 24 2 24 Frame NEMA 56HZ 56HZ 56HZ 56HZ 56HZ Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 NEMA National Electrical Manufacturers Association Table 20 Fan Motor Data FAS FHS Alternate Motor Single Speed SI UNIT FAS FHS 072 FAS FHS 091 FAS FHS 120 FAS 150 FAS FHS 180 208 230 1 60 Speed r s 28 75 28 75 Shaft kW 1 79 1 79 Frame NEMA 56Y 56Y Shaft Dia mm 15 9 15 9 208 230 3 60 and 460 3 60 Speed r...

Страница 29: ... in 7 8 7 8 7 8 1 1 8 1 1 8 Table 23 Motor Efficiency FAS Two Speed Motor MOTOR HP EPACT MINIMUM MOTOR EFFICIENCY 2 4 80 0 2 9 86 5 3 7 83 6 5 0 89 5 89 5 EPACT Energy Policy and Conservation Act of 1992 Table 24 Fan Motor Data FAS Standard Motor Two Speed SI UNIT FAS072 FAS091 FAS120 FAS150 FAS180 208 230 3 60 and 460 3 60 Speed r s 28 00 28 00 28 00 28 92 29 17 Shaft kW 1 79 1 79 1 79 2 16 2 76 ...

Страница 30: ...56HY 56HY 184T Shaft Dia in 7 8 7 8 7 8 1 1 8 Table 28 Motor Efficiency FHS Two Speed Motor MOTOR HP EPACT MINIMUM MOTOR EFFICIENCY 1 7 82 0 2 4 80 0 2 9 86 5 3 7 83 6 3 7 87 9 5 0 89 5 87 9 EPACT Energy Policy and Conservation Act of 1992 Table 29 Fan Motor Data FHS Standard Motor Two Speed SI UNIT FHS072 FHS091 FHS120 FHS180 208 230 3 60 and 460 3 60 Speed r s 28 00 28 00 28 17 29 17 Shaft kW 1 ...

Страница 31: ...728 537 728 Max Allowable Speed rpm 1200 1200 1200 1200 1200 Change per 1 2 Turn of Moveable Motor Pulley Flange 19 6 19 6 19 7 19 1 19 1 MAX FULL TURN FROM CLOSED POSITION 5 5 5 5 5 SHAFTS CENTER DISTANCE IN 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 Table 32 High Static Drive Data 60 Hz English UNIT FAS FHS 072 FAS FHS 091 FAS FHS 120 FAS 150 FAS FHS 180 MOTOR DRIVE Motor Pulley...

Страница 32: ... 1 14 4 9 0 12 1 9 0 12 1 Max Allowable Speed r s 20 0 20 0 20 0 20 0 20 0 Change per 1 2 Turn of Moveable Motor Pulley Flange 0 327 0 327 0 328 0 318 0 318 MAX FULL TURN FROM CLOSED POSITION 5 5 5 5 5 SHAFTS CENTER DISTANCE MM 265 313 265 313 265 313 265 313 265 313 Table 34 High Static Drive Data 60 Hz SI UNIT FAS FHS 072 FAS FHS 091 FAS FHS 120 FAS 150 FAS FHS 180 MOTOR DRIVE Motor Pulley Pitch...

Страница 33: ...16 893 1 34 3000 579 0 70 621 0 79 695 0 96 759 1 12 818 1 30 874 1 47 928 1 66 3400 646 0 99 683 1 09 752 1 29 813 1 48 869 1 67 920 1 86 970 2 06 3750 705 1 31 739 1 42 804 1 63 862 1 85 915 2 05 964 2 26 1011 2 48 FAS120 FHS120 3000 421 0 35 592 0 73 670 0 90 737 1 06 797 1 23 854 1 41 908 1 59 3500 626 0 98 664 1 08 735 1 28 798 1 48 855 1 67 908 1 87 958 2 07 4000 706 1 42 738 1 54 803 1 77 8...

Страница 34: ...136 2 03 1181 2 22 2600 950 1 53 1005 1 72 1057 1 92 1107 2 13 1154 2 33 3000 980 1 86 1031 2 06 1081 2 27 1129 2 49 1175 2 72 3400 1018 2 26 1065 2 48 1111 2 70 1156 2 93 3750 1057 2 69 1101 2 92 1144 3 15 1186 3 39 FAS120 FHS120 3000 961 1 78 1012 1 98 1062 2 19 1111 2 41 1158 2 64 3500 1005 2 27 1052 2 49 1098 2 71 1142 2 94 1186 3 18 4000 1058 2 90 1101 3 13 1143 3 36 1184 3 60 4500 1116 3 66 ...

Страница 35: ... 12 66 0 84 13 64 0 97 14 57 1 10 15 47 1 24 1600 10 76 0 74 11 39 0 81 12 54 0 96 13 55 1 10 14 48 1 24 15 34 1 39 16 17 1 53 1770 11 74 0 97 12 32 1 06 13 40 1 22 14 37 1 38 15 25 1 53 16 07 1 69 16 86 1 85 FAS120 FHS120 1420 7 02 0 26 9 86 0 54 11 17 0 67 12 28 0 79 13 29 0 92 14 23 1 05 15 14 1 19 1650 10 44 0 73 11 06 0 80 12 25 0 96 13 31 1 10 14 25 1 25 15 13 1 39 15 96 1 54 1890 11 76 1 06...

Страница 36: ... 19 68 1 66 1230 15 84 1 14 16 75 1 28 17 62 1 43 18 45 1 58 19 24 1 74 1420 16 34 1 38 17 19 1 54 18 01 1 70 18 81 1 86 19 59 2 03 1600 16 97 1 69 17 76 1 85 18 52 2 02 19 27 2 19 1770 17 61 2 01 18 35 2 18 19 07 2 35 19 77 2 53 FAS120 FHS120 1420 16 02 1 33 16 87 1 48 17 71 1 64 18 52 1 80 19 30 1 97 1650 16 76 1 70 17 53 1 85 18 29 2 02 19 04 2 19 19 77 2 37 1890 17 64 2 16 18 35 2 33 19 05 2 5...

Страница 37: ...ters in larger units that have 2 fans follow the preceding steps but use the factory supplied filter hook to slide filters within reach for removal The filter hook is shipped inside the unit in the filter track Fig 26 Remove Filter Retainer Clip Fig 27 Filter Removal Replacement CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this CAUTION can result in premature wear and damage to equipment DO N...

Страница 38: ...Specifications are subject to change without notice FAS FHS 072 180 01SI Rev A 2022 Carrier Lewisburg TN 37091 USA Replaces 50801160301 ...

Страница 39: ... WIRING TERMINALS including main power supply TIGHT Y N ______________ HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS Y N _________ INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N _________ ARE PROPER AIR FILTERS IN PLACE Y N ______________ HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N ___________ DO THE FAN BELTS HAVE PROPER TENSIO...

Страница 40: ..._ ENTERING OUTDOOR UNIT AIR TEMP ______________ ____________ LEAVING OUTDOOR UNIT AIR TEMP ______________ ____________ INDOOR UNIT ENTERING AIR DB TEMP ______________ ____________ INDOOR UNIT ENTERING AIR WB TEMP ______________ ____________ INDOOR UNIT LEAVING AIR DB TEMP ______________ ____________ INDOOR UNIT LEAVING AIR WB TEMP ______________ ____________ COMPRESSOR AMPS L1 L2 L3 ____ ____ ____...