FAS-FHS-072-180-01SI Rev. A
Specifications are subject to change without notice.
CL-1
START-UP CHECKLIST
(SPLIT SYSTEMS WITH FAS/FHS UNITS)
I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO. _________________________ INDOOR: MODEL NO. ______________________
SERIAL NO._______________________________ SERIAL NO. ______________________________
ADDITIONAL ACCESSORIES _______________________________________________________________________
II. PRE-START-UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N)_____________
IF SO, WHERE:___________________________________________________________________________________
________________________________________________________________________________________________
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)_______
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)________
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)________
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)_________
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)__________
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)___________
CONTROLS
ARE THERMOSTAT(S) & INDOOR FAN CONTROL WIRING CONNECTIONS MADE & CHECKED? (Y/N)_________
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)______________
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)_________
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)_________
ARE PROPER AIR FILTERS IN PLACE? (Y/N)______________
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)___________
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)_____________
PIPING
FAS/FAHS
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N)__________
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (FAS) OR OUTDOOR UNIT
(FHS) COILS AS REQUIRED? (Y/N)___________
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)____________
LOCATE, REPAIR, AND REPORT ANY LEAKS. ______________
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)_____________
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N)____________
NOTE: To avoid injury to personnel and damage to equipment or prop
-
erty when completing the procedures listed in this start-up checklist,
use good judgment, follow safe practices, and adhere to the safety con
-
siderations/information as outlined in preceding sections of this Instal
-
lation, Start-Up, and Service document.