FAS-FHS-072-180-01SI Rev. A
Specifications subject to change without notice.
35
LEGEND
Bold
indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underlining indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables to complete selection.
* For FHS120, these operating points require different motor and drive
combinations.
NOTES:
1. Maximum allowable fan speed is 20 r/s for all sizes.
2. Fan performance is based on deductions for wet coil, clean 51 mm
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. Refer to fan motor and drive tables for additional data.
Table 37 — Fan Performance Data — FAS/FHS 0-300 Pa ESP, 60 Hz — SI
UNIT
AIRFLOW
(L/s)
EXTERNAL STATIC PRESSURE (Pa)
0
50
100
150
200
250
300
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
FAS072
FHS072
850
6.98
0.16
7.86
0.19
9.40
0.27
10.81
0.37
12.11
0.47
13.29
0.57
14.36
0.69
990
7.84
0.23
8.64
0.27
10.03
0.36
11.31
0.46
12.52
0.57
13.65
0.69
14.71
0.81
1130
8.73
0.33
9.46
0.38
10.75
0.48
11.91
0.59
13.01
0.70
14.07
0.83
15.08
0.96
1270
9.63
0.45 10.31
0.51
11.51
0.62
12.58
0.74
13.60
0.86
14.58
0.99
15.53
1.13
1420
0.55
0.61 11.18
0.67
12.30
0.80
13.31
0.92
14.26
1.05
15.17
1.19
16.05
1.33
FAS091
FHS091
1060
4.83
0.07
8.50
0.29
9.91
0.38
11.15
0.48
12.32
0.59
13.44
0.71
14.50
0.83
1230
5.81
0.14
9.35
0.41
10.67
0.52
11.81
0.63
12.88
0.74
13.90
0.87
14.89
1.00
1420
9.65
0.52 10.35
0.59
11.59
0.71
12.66
0.84
13.64
0.97
14.57
1.10
15.47
1.24
1600
10.76
0.74 11.39
0.81
12.54
0.96
13.55
1.10
14.48
1.24
15.34
1.39
16.17
1.53
1770
11.74
0.97 12.32
1.06
13.40
1.22
14.37
1.38
15.25
1.53
16.07
1.69
16.86
1.85
FAS120
FHS120
1420
7.02
0.26
9.86
0.54
11.17
0.67
12.28
0.79
13.29
0.92
14.23
1.05
15.14
1.19
1650
10.44
0.73 11.06
0.80
12.25
0.96
13.31
1.10
14.25
1.25
15.13
1.39
15.96
1.54
1890
11.76
1.06 12.31
1.15
13.38 1.32*
14.37 1.49*
15.28
1.66
16.11
1.83
16.89
1.99
2120
13.10 1.48* 13.59 1.58* 14.55
1.78
15.48
1.97
16.34
2.17
17.14
2.35
17.89
2.54
2360
14.45
2.01 14.89
2.12
15.76
2.34
16.62
2.56
17.43
2.77
18.20
2.98
18.92
3.19
FAS150
1770
6.84
0.32
7.78
0.41
9.46
0.62
10.82
0.83
12.02
1.05
13.13
1.28
14.19
1.53
2030
7.58
0.46
8.40
0.55
9.98
0.78
11.31
1.03
12.47
1.27
13.52
1.52
14.51
1.78
2360
8.57
0.69
9.27
0.79
10.68
1.04
11.96
1.31
13.09
1.60
14.11
1.88
15.05
2.17
2690
9.59
0.99 10.20
1.10
11.44
1.36
12.64
1.66
13.74
1.98
14.74
2.30
15.65
2.63
2950
10.40
1.28 10.96
1.39
12.09
1.67
13.21
1.98
14.27
2.33
15.25
2.68
16.15
3.03
FAS180
FHS180
2120
7.28
0.45
8.05
0.54
9.60
0.75
11.00
1.00
12.21
1.26
13.28
1.15
14.27
1.78
2500
8.32
0.71
8.97
0.80
10.29
1.02
11.59
1.30
12.78
1.59
13.84
1.89
14.80
2.19
2830
9.25
1.00
9.83
1.10
10.99
1.33
12.16
1.62
13.29
1.93
14.34
2.27
15.30
2.60
3210
10.33
1.42 10.85
1.54
11.87
1.78
12.90
2.07
13.93
2.40
14.93
2.76
15.87
3.14
3540
11.29
1.88 11.77
2.01
12.69
2.27
13.62
2.56
14.56
2.90
15.49
3.27
16.40
3.67
ESP
— External Static Pressure
Factory-Supplied Pressure Drop — SI
UNIT
AIRFLOW (L/s)
PRESSURE
DROP (Pa)
FAS072
FHS072
850
13
1150
20
1450
28
FAS091
FHS072
1000
17
1400
27
1800
38
FAS120
FHS120
1450
28
1900
42
2350
56
FAS150
1750
15
2350
24
3950
33
FAS180
FHS180
2100
20
2800
30
3500
42