Replacing Filters
Filters can be removed and installed from either side of the
unit. Install new filters in units that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 26).
3. Remove old filters by lifting and tilting them out of the fil
-
ter track. (See Fig. 14 and 27.)
4. Reverse the procedure to install new filters.
To install new filters in larger units that have 2 fans, follow
the preceding steps, but use the factory-supplied filter hook
to slide filters within reach for removal. The filter hook is
shipped inside the unit in the filter track.
Fig. 26 — Remove Filter Retainer Clip
Fig. 27 — Filter Removal/Replacement
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION can result in premature
wear and damage to equipment.
DO NOT OPERATE THE UNIT WITHOUT THE RE
-
TURN AIR FILTERS IN PLACE.
Dirt and debris can collect on heat exchangers and coils
possibly resulting in a small fire. Dirt buildup on compo
-
nents can cause excessive current used resulting in mo
-
tor failure.