background image

SMARTY XV

EN 

MOUNTING AND INSTALLATION INSTRUCTION

Содержание SMARTY XV Series

Страница 1: ...SMARTY XV EN MOUNTING AND INSTALLATION INSTRUCTION...

Страница 2: ...RECOMMENDATIONS FOR THE MAINTENANCE OF VENTILATION SYSTEM 14 6 3 COVER OPENING 14 6 4 FILTERS MAINTENANCE 15 6 5 FANS MAINTENANCE 15 6 6 HEAT EXCHANGER MAINTENANCE 16 6 7 BYPASS DAMPERS AND PRE HEATER...

Страница 3: ...n about the unit Figure 2 1 Technical label 1 Logo 2 Product code SKU 3 Product name 4 Technical data 5 Production place 6 production date 7 Serial number Figure 2 2 Indication for duct connection ODA...

Страница 4: ...touch heating elements until they haven t cooled down Some devices are heavy thus one should be very careful while transporting and installing Use suitable lifting equipment While connecting electric...

Страница 5: ...o C to 40 o C For the cold climate zones air temperatures below 2 o C integrated or optional pre heater is required if airflow misbanancing is disabled Product name Control board Type Heat recov ery T...

Страница 6: ...niMCB basic miniMCB miniMCB basic Insulation of walls mm 30 30 30 30 30 30 Exhaust air filter class dimensions LxWxH mm MPL 270x187x25 Coarse 65 MPL 475x180x25 Coarse 65 MPL 475x180x25 Coarse 65 Suppl...

Страница 7: ...o C 5 o C Maximum ambient air temperature 40 o C 40 o C 40 o C 40 o C 40 o C 40 o C Installation indoor only indoor only indoor only indoor only indoor only indoor only 4 5 STANDART PACKAGE OF COMPONE...

Страница 8: ...C and 30 C The place of storage must be protected against dirt and water The units must be transported to the storage or installation site using forklifts The storage is not recommended for a period...

Страница 9: ...ptional Figure 5 4 2 SMARTY XV miniMCB basic Only heater or preheater can be connected at a time Check the manual for details Optional LIST OF COMPONENTS C Plate heat exchanger KE1 Electric heater PV...

Страница 10: ...he unit and the first branch of the air duct in the supply air duct must be 1xD in air exhaust duct 3xD where D is diameter of the air duct It is recommended to use the accessories holders This will r...

Страница 11: ...00 mm 5 7 FLOOR MOUNTING Figure 5 7 1 floor mounting optional accessory required 5 8 MOUNTING ON WALL b 30 mm a c d 90 90 Figure 5 8 1 mounting on the wall 5 9 DRAINAGE Before every heating season the...

Страница 12: ...egrees 1 meter of pipe must be bended 60 mm downwards Before turning on AHU 1 the draining system should be filled up with at least 0 5 l of water pipe loop 3 must be always filled with water also che...

Страница 13: ...et distribution devices Prior to carrying out any ventilation unit installation and connection activities until its hand over to the customer the unit must be disconnected from the power network After...

Страница 14: ...rs do not cause noise when rotated by hand Make sure that the fastening screws are not loose and free of mechanical damage Check electrical connections and make sure that these are se cured properly a...

Страница 15: ...rom X16 X2 X4 Detach fan from the unit Impeller should be specially checked for buil up material or dirt which may cause an imbalance Excessive imbalance can lead to accelerated wear on motor bearings...

Страница 16: ...warm soapy water do not use soda Then rinse it with weak hot water stream too strong stream can fold the plates Place back the heat exchanger only when it is completely dry Figure 6 6 1 Smarty 2XV Fi...

Страница 17: ...the marking on the controller terminals is not visible follow the PCB information provided in this passport see miniMCB description Fig 2 and Fig 3 1 2 3 6 9 SMARTY 4XV SWITCHING POWER SUPPLY MAINTEN...

Страница 18: ...IONS All MCB control boards has the same software with all functions included Full function list and description you can find on the MCB control board manual However operation and control of the devic...

Страница 19: ...ACC003807 EKA NIS 125 0 6 1 f ACC000319 EKA NIS 125 0 9 1 f ACC000320 EKA NIS 125 1 2 1f ACC003803 EKA NIS 125 1 5 1 f ACC000321 EKA NIS 125 1 8 1 f ACC000322 EKA 160 0 3 1 f ACC003723 EKA 160 0 6 1 f...

Страница 20: ...or circular Mute 160x600 Smarty 3 4XV Mute 160x600 FIT000289 Attenuator circular Mute 160x900 Smarty 3 4XV Mute 160x900 FIT000290 Dampers circular shut off sealed blade d125 SKG A 125 FIT000201 Damper...

Страница 21: ...EKA NIS connection Automatic and manual protection shall be connected to EX1 controllers X23 connector if the electric heater is equipped with these connection terminals Otherwise jumpers are install...

Страница 22: ...2 units have one connection of external electrical heater pre heater In factory settings connection is dedicated for the pre heater but can be configured for the heater Heater pre heater can be contro...

Страница 23: ...EN 23 SMARTY XV v2020 2 EKA NIS connection...

Страница 24: ...he environment of the MB Gateway WEB application service or on the ST SA Control panel Settings in the environment of the MB Gateway WEB application service Change the settings as follows Service pass...

Страница 25: ...ater protection Set the manual and automatic protection statuses according to the standards it should be NC 6 Go to Menu Service Digital inputs Preheater protection Set the manual and automated protec...

Страница 26: ...sensors Sensors connection 24VDC AI4 0 10V GND 1 2 3 4 5 6 7 8 AO1 GND Vin Transmiter 1 Supply air CO2 or RH input 0 10VDC 24VDC GND 1 2 3 AI1 0 10V Vin GND AO1 Transmitter 2 Smarty 3XV 1 1 and Smart...

Страница 27: ...ncentration drowsi ness headache etc 1500 1000 Pettenkofer limit Pettenkofer limit Disturbs 500 Pleasant 0 0 1 2 3 4 Duration of the presence in the room in hours Closed windows Controlled ventilation...

Страница 28: ...ermination resistor On Off 8 1 8 FIRE PLACE CONNECTION SMARTY XV 1 1 Wiring diagram Automation controller C zone X23 connector 1 2 3 4 5 6 7 8 Fire Place II DI4 12VDC 12VDC DI3 Fire Place I LED indica...

Страница 29: ...Jumper 7 Punktyrine linija pa ym tus komponentus ir kabelius pajungia SALDA arba vartotojas Components and cables marked with the dash line connected by SALDA or customer Bypass actuator for versions...

Страница 30: ...30 EN SMARTY XV v2020 2 Figure 8 1 9 2 Smarty 2XV 1 1 Smarty 2XV 3XV 4XV 1 2 219 1017 0 1 2 PS...

Страница 31: ...EN 31 SMARTY XV v2020 2 C H C C H C Figure 8 1 9 3 Smarty 2XV 1 1 Smarty 2XV 3XV 4XV 1 2 219 1017 0 1 3 PS...

Страница 32: ...AME DATE UAB SALDA Drawing Book CHECKED BY 1 1 2 3 4 4 5 6 7 7 EI D Aleksandravi ius EI A klenikas Pyn l Smarty 3XV PE 0k 221 1011 0 1 0 PS 0k Principle connection scheme 8 01 2015 11 24 2015 11 24 20...

Страница 33: ...35 Red 0 35 Yellow 0 35 Blue 0 35 Yellow 0 35 Blue 0 35 Brown Black 0 5 Green yellow 0 5 Blue 0 5 Brown Black 0 5 Blue 0 5 Green yellow 0 5 Figure 8 1 9 6 Smarty 2XV 3XV Fans MiniMCB DRAWN BY CHECKED...

Страница 34: ...1 PE X12 2 N L1 X12 3 DO2 L L2 N2 miniMCB V0 3 01 6 3 X2 5 GND X2 6 AO3 0 10V N2 miniMCB V0 3 01 5 3 External preheater Control 0 10V Power over 2kW 2f 400V K1 A1 A2 230VAC 11 14 K1 K1 1 2 3 4 PE L1 L...

Страница 35: ...NTC X6 2 GND N1 miniMCB V0 3 G1 L N PE V V PE X9 1 24VDC_IN X9 2 GND X9 3 PE N1 miniMCB V0 3 X3 1 24VDC X3 2 STEP_B X3 3 STEP_B X3 4 STEP_A X3 5 STEP_A X3 6 24VDC N1 miniMCB V0 3 X5 5 DI7 X5 6 12VDC N...

Страница 36: ...4 12VDC N1 miniMCB V0 3 X8 1 GND X8 2 24VDC_P X8 3 12VDC X8 4 3 3VDC X8 5 2 5VDC_REF X8 6 GND X8 7 I2C_CDA X8 8 I2C_SCL N1 miniMCB V0 3 X22 1 GND X22 2 24VDC X22 3 12VDC X22 4 3 3VDC X22 5 2 5VDC_REF...

Страница 37: ...1 miniMCB V0 3 Punktyrine linija pa ym tus komponentus ir kabelius pajungia SALDA arba vartotojas Components and cables marked with the dash line connected by SALDA or customer Optional CO2 input 0 10...

Страница 38: ...nsor DTJ ACC002486 Temp sensor TJ ACC002560 By pass drive 15 D SEE 202 GPYSM221_0_1007 Heat exchanger ZSLPLRU0001 Fan supply Smarty 3XV 1 1 GPUVM224_1032_1032 Fan supply Smarty 3XV 1 2 GPUVM224_1034_1...

Страница 39: ...EN 39 SMARTY XV v2020 2 Doors GPUD232_1028_0 By pass damper Smarty 4XV 1 1 GPUSK227_1004_1016 By pass damper Smarty 4XV 1 2 GPUSK227_1006_1016...

Страница 40: ...erat ing or malfunctioning if installed Too low air flow in air ducts activates auto matic protection Check if air filters are not clogged Check if fans are rotating Manual protection is activated Pos...

Страница 41: ...E 350 2085 Central demand control opt with 1 sensor 0 85 14 0 E 281 2098 Local demand control opt with 2 sensors 0 65 17 2 E 164 2126 Declared typology Bidirectional Type of drive installed fan Varia...

Страница 42: ...demand control opt with 1 sensor 0 85 14 0 E 281 2098 Local demand control opt with 2 sensors 0 65 Declared typology Bidirectional Type of drive installed fan Variable Type of heat recovery system Rec...

Страница 43: ...sensor 0 65 17 5 E 138 2093 Declared typology Bidirectional Type of drive installed fan Variable Type of heat recovery system Recuperative Thermal efficiency of heat recovery 86 9 Maximum flow rate m...

Страница 44: ...emand control opt with 1 sensor 0 85 14 7 E 235 2056 Local demand control opt with 2 sensors 0 65 Declared typology Bidirectional Type of drive installed fan Variable Type of heat recovery system Recu...

Страница 45: ...sensor 0 65 15 2 E 212 2047 Declared typology Bidirectional Type of drive installed fan Variable Type of heat recovery system Recuperative Thermal efficiency of heat recovery 82 Maximum flow rate m 3...

Страница 46: ...demand control opt with 1 sensor 0 85 10 9 E 362 1996 Local demand control opt with 2 sensors 0 65 Declared typology Bidirectional Type of drive installed fan Variable Type of heat recovery system Re...

Страница 47: ...The following harmonized standards are applied in applicable parts LST EN ISO 12100 2011 Safety of machinery General principles for design Risk assessment and risk reduction LST EN 60204 1 2006 Safety...

Страница 48: ...e equipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic errors or i...

Страница 49: ...49 SMARTY XV v2020 2...

Страница 50: ...50 SMARTY XV v2020 2...

Страница 51: ...51 SMARTY XV v2020 2...

Страница 52: ...INTENANCE TABLE Product name SERIAL number Instalation Interval Date Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product label At least...