6.4. FILTERS MAINTENANCE
Figure 6.4.1. Smarty 2XV
Figure 6.4.2. Smarty 3XV/4XV
Smarty 2X V filters:
In order to remove the filters, use key to open
the doors and take off the filters. Use Coarse 65% (ePM1 70% -
optional) filters.
Smarty 3-4X V filters
: In order to remove the filters, open filter
cover by pulling the strap and take off the filters. Use Coarse 65%
(ePM1 70% - optional) filters.
After changing the filters, please reload the filter timer. Instruction on reloading, you may find in manual of control panel or
on our website www.salda.lt
Change the filters every 3-4 months or according to the notification on the control device.
6.5. FANS MAINTENANCE
Maintenance should be performed only by experienced and trained staff. The fan should be inspected and cleaned at least once a year.
• Be sure the fan is disconnected from power source before performing any maintenance or repair.
•
Observe staff safety regulations during maintenance and repair.
• The motor is of heavy duty ball bearing construction. The motor is completely sealed and requires no lubrication. Supplied air fan from X15, X2,
X4. Extract air fan from X16, X2, X4.
• Detach fan from the unit.
• Impeller should be specially checked for buil-up material or dirt which may cause an imbalance. Excessive imbalance can lead to accelerated
wear on motor bearings and vibration.
• Clean impeller and inside housing with mild detergent, water and damp, soft cloth.
• Do not use high pressure cleaner, abrasives, sharp instruments or caustic solvents that may scratch or damage housing and impeller.
•
Do not plunge the motor into any fluid while cleaning impeller.
• Make sure, that impeller’s balance weights are not moved.
• Make sure the impeller is not hindered.
• Mount the fan back into the unit. Connect the fan to power supply source.
•
If after maintenance the fan does not start or stop itself, contact the producer. Malfunction of the fan can be identified according to the pressure
in the system (when pressure switches are connected). When there is a folt in fans’ motor, any separate notice is shown on the control panel.
Be sure the unit is disconnected from power source before performing any maintenance or repair.
- Remove the fan connectors from the control board. Supplied air fan from X15, X2, X4. Extract air fan from X16, X2, X4.
Note:
- X2, X4 are common for both fans.
- Reassembly shall be executed in the reverse order.
X2
X15
X16
X4
The wiring diagram can be found in the "MCB miniMCB technical manual".
Содержание SMARTY XV Series
Страница 1: ...SMARTY XV EN MOUNTING AND INSTALLATION INSTRUCTION...
Страница 23: ...EN 23 SMARTY XV v2020 2 EKA NIS connection...
Страница 30: ...30 EN SMARTY XV v2020 2 Figure 8 1 9 2 Smarty 2XV 1 1 Smarty 2XV 3XV 4XV 1 2 219 1017 0 1 2 PS...
Страница 31: ...EN 31 SMARTY XV v2020 2 C H C C H C Figure 8 1 9 3 Smarty 2XV 1 1 Smarty 2XV 3XV 4XV 1 2 219 1017 0 1 3 PS...
Страница 49: ...49 SMARTY XV v2020 2...
Страница 50: ...50 SMARTY XV v2020 2...
Страница 51: ...51 SMARTY XV v2020 2...