62
Recommended periodical checks sheet
intervention frequency (months)
1
6
12
1 presence corrosion
X
2 panel fixing
X
3 fans fixing
X
4 coil cleaning
X
5 bowl cl sanitisation
X
6 outflow test
X
7 air filters cleaning/inspection
X
8 air flow rate measurement
X
9 channelling: anti-vibration devices and fastenings check
X
10 power supply cable isolation and fastening check
X
11 earth cable check
X
12 electric control board cleaning
X
13 power remote controls state
X
14 clamps closure, cables isolation integrity
X
15 phases unbalancing and power supply voltage (vacuum and loaded)
X
16 absorption of the individual electric loads
X
17 compressors carter heaters test
X
18 leaks control *
*
19 cooling circuit work parameters detection
X
20 Saftey valve *
*
21
protective equipment test: safety valves, pressure switches, thermostats, flow meters, etc.
X
22
protective equipment test: setpoint, climatic compensations, power slicing, air flow rate variations
X
23
control devices test: alarms signal, thermometers, probes, pressure gauges, etc.
X
24
electrical heaters check - option
X
25
water coil check - option
X
NOTE
*Refer to the local regulations. Companies and technicians performing installation, maintenance/repair,
leak control and recovery operations must be CERTIFIED as set out by the local regulations.
Содержание CSRN-XHE2 Series
Страница 1: ...CSRN XHE2 49 4 110 4 R 410A M07V40B13 07 11 20 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Страница 75: ...Dimensional drawings 75...
Страница 77: ...Dimensional drawings 77...
Страница 79: ...Dimensional drawings 79...
Страница 81: ...Dimensional drawings 81...
Страница 83: ...Dimensional drawings 83...
Страница 85: ...Dimensional drawings 85...
Страница 87: ...Dimensional drawings 87...
Страница 89: ...Dimensional drawings 89...
Страница 91: ...Dimensional drawings 91...