background image

31

  

Delivery air flow management 

Standard mode 

The fan rotation speed remains constant in all heat load 
conditions and operation modes. 

Eco mode 

The fan rotation speed  (or the delivery air flow if the constant 

flow option is present) stays constant as the thermal load varies 
and is shutdown when setpoint is fulfilled. 

Constant air flow 
Option 

The delivery air flow stays constant as the thermal load varies 
and the pressure drops of unit and the system. 
The ventilation remains active even when the setpoint is fulfilled.  

Variable airflow  
Option  

The air flow supply varies depending on the heat load, up to a 

minimum value compatible with the distribution system and the 
chosen air diffusion.  
The ventilation remains active even when the setpoint is fulfilled.  
Calibration:  
1  check the doors and windows of the serviced room are closed  
2  calibration must be carried out with unit all in recirculation: 

during the first 20 minutes from start-up, the unit is in full 
recirculation  

3  set the nominal air flow range  

 menu 

SUPPLY VENTILATION 

 

   

par 261 SfQSet  (m3/h)  

4  set the reduced air flow 

 menu 

VENTILATION

  

 

   

par 294 RfFctRimod  

   

reduction at xx% of the nominal flow rate  

Air flow setting 

Standard mode 

The fan speed 

setting must be checked by a service centre 

authorised by Clivet 
The real unit flow is according to the aeraulic system features. 
Before checking, make sure that the system has been completed 
in all its parts (shunts, dampers, grilles, diffusers etc.). 
Calibration must be carried out with unit all in recirculation. 
During the first 20 minutes from start-up, the unit is in full 
recirculation  
Set the flow rate : 

 

menu supply ventilation  

 

 

par 265 SfFanSpeedOut  (%)  

nominal = par 

265

 

SfFanSpeedOut

 

nominal = par 261 SfQSet   

min = par 

294

 

RfFctRimod

 

ECO Mode 

Standard mode 

Variable airflow  

FanSpeed

 

Constant airflow 

Air

fl

ow

 

Air

fl

ow

 

Air

fl

ow

 

Содержание CSRN-XHE2 Series

Страница 1: ...CSRN XHE2 49 4 110 4 R 410A M07V40B13 07 11 20 MANUAL FOR INSTALLATION USE AND MAINTENANCE...

Страница 2: ...ime with highly reliable efficient high quality and safe solutions The target of the company is to offer advanced systems that assure the best comfort and reduce energy consumption as well as the inst...

Страница 3: ...Con gurations 7 Reception 10 Selecting the installation site 12 Water connections 17 Aeraulic connections 20 Electrical connections 21 Start up 28 Control 36 Maintenance 60 Decommissioning 67 Residua...

Страница 4: ...se damages to things and injuries people Intended use Use the unit only civil air conditioning keep to the limits foreseen in the technical schedule and in this manual The manufacturer accepts no resp...

Страница 5: ...vements may imply manual data changes Visit manufacturer web site for updated data Indications for the User Keep this manual with the wiring diagram in an accessible place for the operator Note the un...

Страница 6: ...refrigerant charge manufacturer logo and address The matriculation plate must never be removed It contains fluorinated greenhouse gases Serial number It identifies uniquely each unit Must be quoted wh...

Страница 7: ...air S Supply air FA Fresh air 1 G4 efficiency filters electronic filters option or F7 filter option 2 Handling exchanger 3 Supply fan section 4 Hot gas reheating exchanger 5 Electric heaters 6 Thermod...

Страница 8: ...ger 5 Electric heaters 6 Thermodynamic recovery on exhaust air 7 Exhaust damper 8 Exhaust fan section 9 Thermodynamic recovery on exhaust air R Return air S Supply air FA Fresh air EX Exhaust air 1 G4...

Страница 9: ...stage standard G4 ISO 16890 Coarse 60 2 filtering stage option F7 ISO 16890 ePM1 55 2 filtering stage option FES electronic filters ISO 16890 ePM1 90 Filters nomenclature according to EN ISO 16890 Sta...

Страница 10: ...damage you found and quote this sentence Conditional acceptance clear evidence of deficiencies damages during transport wontact by fax and registered mail with advice of receipt to supplier and the c...

Страница 11: ...to guarantee the safety of the personnel present and the of material Verify unit weight and handling equipment lifting capacity Identify critical points during handling disconnected routes flights st...

Страница 12: ...e any leaking gas cannot enter buildings or stagnate in closed areas In the latter case observe the rules for machinery rooms ventilation leak detection etc Installation standards install the unit rai...

Страница 13: ...Avoid the accumulations of snow and ice in front of the exhaust air outlet Pressure relief valve gas side The installer is responsible for evaluating the opportunity of installing drain pipes in compl...

Страница 14: ...n the specific installation requirements the length of the chimney can be increased with suitable joints and fittings not supplied by Clivet Gas connection Read the gas heating module manual Connectio...

Страница 15: ...ce of air bypass A Apply the flat adhesive gasket15x5 on the Gas Module flange perimeter to guarantee the absence of air bypass B Fix with screws the flue supporting bracket to the GM frontal panel C...

Страница 16: ...16 Gas use features Connections performed by costumer A rooftop B supply fan C gas module D connecting cables E electrical panel terminal XG...

Страница 17: ...pings Connect the condensate discharge to a sewerage drainage network DO NOT use white water or drainage networks to avoid the aspiration of odours in the case of evaporation of water contained in the...

Страница 18: ...ater Respect the limits indicated in the table No relation can be demonstrated between water hardness and conductivity Limit values for the supply water conductivity medium low medium high min max min...

Страница 19: ...19 Heating coil Option Max operating pressure 10 bar A drain cock B vent valve Provided by the costumer 1 anti vibration devices 2 piping supports 3 Shut off valves 1 3 A B 2...

Страница 20: ...portunity of equipping them with deflectors in particular with high air speed or bends with reduced radius Treated air channelling The internal surface of the channel must be smooth enable its washing...

Страница 21: ...admitted conditions F L I full load input full load power input at max admissible condition Electrical wiring diagram Nr Connections refer to the unit electrical diagram the number of the diagram is...

Страница 22: ...Do not lay the cables parallel to other cables cable crossings are possible only if laid at 90 Connect the screen to the ground only if there aren t disturbances Guarantee the continuity of the scree...

Страница 23: ...e only if the unit is equipped with a hot water integration coil HLC Compressor status signal lamp HLHE Warning light of the heat pump operating status HLVE Indicating light of the return and or suppl...

Страница 24: ...operty Set the IP address 192 168 1 100 Set Subnet mask as 255 255 255 0 confirm OK Enter Start Windows button Write the command cmd and enter do it Write and run the command Ping 192 168 1 42 if will...

Страница 25: ...ace A user interface B B1KNX bus max 350 mt twisted pair with shield 0 8 mm EIB KNX cable marking recommended C power supply unit N125 11 5WG1 125 1AB11 C1 AC 120 230 V 50 60 Hz Distance up to 350 mt...

Страница 26: ...an internal terminator it must be enabled using the specific jumper dip switch or link The cable must have insulation features and non flame propagation in accordance with applicable regulations The R...

Страница 27: ...software error fixed hardware error LED BUS communication with LONWORK green communication ok yellow startup flashing communicating not possible red communication down LONWORK CABLE TYPES Echelon allo...

Страница 28: ...make sure no tension is present After turning off the power wait at least 5 minutes before accessing to the electrical panel or any other electrical component Before accessing check with a multimeter...

Страница 29: ...any oil stains can be symptom of leaks caused by for example transport handling or other 2 Check the cooling circuit is pressurised use the machine pressure gauges if present or service pressure gauge...

Страница 30: ...within in the operating limits Start up the unit With unit operating in stable conditions check Voltage Total absorption of the unit Absorption of the single electric loads Scroll compressor The Scro...

Страница 31: ...erviced room are closed 2 calibration must be carried out with unit all in recirculation during the first 20 minutes from start up the unit is in full recirculation 3 set the nominal air flow range me...

Страница 32: ...rved area in case it is temporarily not used which can for example occur at night The ECO mode can be activated manually from keyboard with MODE menu automatically by means the time slots automaticall...

Страница 33: ...m start up the unit is in full recirculation 3 On display view the state PDiffRipresa_X4 AI 955 value of the return load losses 4 Wait for the pressure value to stabilise and take note of the value 5...

Страница 34: ...n off outdoor air shutter closed overpressure shutter closed room kept in depression supply fan off ejection fan on outdoor air shutter closed overpressure shutter open supply fan on ejection fan off...

Страница 35: ...rbed If enabled by signal the greater is the signal the lower is the absorbed electrical power For the connections see the wiring diagram Low set up outdoor temperature Option indicated for very cold...

Страница 36: ...an example see the following Compulsory verification of the first installation only for units assembled on the installer s building site for ex Condensing circuit direct expansion unit Certification...

Страница 37: ...ion are alternated every 2 seconds When the status is OFF changes to the SETPOINT and schedule are blocked Humidifier Dehumidifier mode The Humidifier mode is active If flashing it means the Dehumidif...

Страница 38: ...ManSet xx C Starting from this value the module determines 2 setpoint COOLING manset dead area 2 xx 1 C HEATING manset dead area 2 xx 1 C AUTOMATIC TEMPERATURE SETPOINT The setpoint can also AUTOMATI...

Страница 39: ...scription 0 SetUrCool Relative humidity setpoint in Cool mode 1 SetURHeat Relative Humidity setpoint in Heat mode 2 SetEcoCool Temperature setpoint in cool economy mode 3 SetEcoHeat Temperature setpoi...

Страница 40: ...p _B3 AI 687 2 RH Return_X1 AI 955 3 RH External_X2 AI 955 4 QualityAir_X2 AI 687 5 Nr active compressors 6 ActVcInt 7 Cmd ExternalDamper_X7 AO 687 8 PowerHum Example of status codification Supply tem...

Страница 41: ...ys disabled select to confirm exit 16 3 C 17 00 COD _ _ _ _ T0 ON n key key n key key T0 T5 T1 T6 T2 T7 T3 ALL All keys T4 Key code table T1 OFF ALL OFF ESC 16 3 C 17 00 DATE AND HOUR Press HOUR digit...

Страница 42: ...n cause irreversible damage Type of alarm Code Type Restore ee Electric Automatic eE Electric From Auto to manual EE Electric Manual ii Idraulic Automatic iI Idraulic From Auto to manual II Idraulic M...

Страница 43: ...ing ex days 2 4 5 6 3 select days 2 4 5 6 4 set event 1 event time state Off On Fan 5 set event 2 3 ecc 6 select days 1 3 7 7 set event 1 2 3 ecc The most recent schedule saved overrides the existing...

Страница 44: ...other days of the week are automatically scheduled press Set event 1 example Tuesday 05 30 FAN press starts flashing set event time press set eventt minutes press iset desired mode 0 null 1 OFF 2 ECO...

Страница 45: ...ON FAN 21 00 6 OFF OFF OFF OFF OFF OFF OFF Example day 5 change events 3 and 4 from ON to OFF set eventt minutes press iset desired mode 0 null 1 OFF 2 ECO 3 ON 4 Fan press Press to set other the even...

Страница 46: ...46 press press 4 times event 4 press 3 times starts flashing 003 ON select mode 002 OFF confirm press 2 times to exit 003 15 00 5 16 3 C 17 00 002 15 00 5 003 15 00 5 002 15 00 5...

Страница 47: ...ool COMMON OPERATIONS ON OFF ECO main menu cmd local status scegliere OFF ON ECO PUMP ON change MODE main menu cmd local mode select COOL HEAT change SETPOINT main menu unit parameters setpoint DISPLA...

Страница 48: ...ts number dipend on unit s series The menu is repeated for each refrigerant circuit circuit circuit1 circuit2 thermostatic circuit1 circuit2 Setpoint Menu P0001 ManSet Manual temperature Setpoint P000...

Страница 49: ...be enabled display actual value On pag xy unit parameters service maintenance P0500 1 Setting Select Confirm d01 Monday Scheduled day Active Time 1 xx yy Value 1 Eco Time 2 Value 2 Setting d01 Monday...

Страница 50: ...Util Ok EE003 Guasto P1 Util Fault Press Press alarm log detail eE001 Monitore fase Fault 1 Critico A 14 02 2012 11 30 10 alarm list Reset Passive 1 eE001 Monitore fase Fault Select Confirm Select Co...

Страница 51: ...t EE003 Guasto P1 Util Ok EE003 Guasto P1 Util Fault Alarm cnf AlarmSnapshot 0 Lista allarmi Ordinamento 1 Ora Ordinamento 2 Ora Ordine descrescente Passive Execute Allarmi cnf AlarmSnapshot 0 Lista a...

Страница 52: ...g Circuit C1 Thermostatic C1 Unit option Thermoregulator Integrations Compressor Correction SH Sourse Ventilation Supply fan Defrost Humidity control Recovery renewal Reset usure Sensor settings Seria...

Страница 53: ...5 1 board offline A ee046 Ambient pressure probe failure A ID Description Reset ee101 Circuit 1 module disconnection on Proces A ee102 Thermostatic valve driver timeout A ee104 Thermostatic valve bloc...

Страница 54: ...Source frost M iI220 Source flow M II221 Source frost M fF109 DI Low Pressure A M ff110 Cool Low pressure Pre alarm A ff111 Low Heat Pressure pre alarm A fF112 AI Low Pressure A M fF113 DI High Press...

Страница 55: ...RM 3001 Central POL687 IO Cmd Supply Fan_X5 AO 687 Modulating supply fan control percentage 3001 Central POL687 IO Cmd ExternalDamper_X7 AO 687 External damper opening control percentage 3001 Central...

Страница 56: ...g 3003 Thermoregulator 16 Fch state Freecooling heating status 3003 Thermoregulator 17 Actual request for addition Reg requested for the additions 3003 Thermoregulator 18 Addition state Additions stat...

Страница 57: ...p 2 status 0 Free 1 Active 2 Timed 3 Not enabled 3101 Circuit C1 Stata 1113 Comp 3 status 0 Free 1 Active 2 Timed 3 Not enabled 3101 Circuit C1 Stata 1114 Current cap Capacity currently employed on th...

Страница 58: ...tact 3102 Circuit C1 IO Stata Ovl Source_DL2 DI 985 0 Fault 1 OK Status of the thermal protection contact of the source motors 3102 Circuit C1 IO Stata ElectFilter_X5 DI 985 0 Fault 1 OK Status of the...

Страница 59: ...corrections 3201 Thermostatic C2 Stata 2201 AICalSuctSprHtP Current overheating value calculated 3201 Thermostatic C2 Stata 2202 ECVState 0 Idle 1 ECVAlarm 2 FailSafe 3 Referencing 4 Positioning 5 Po...

Страница 60: ...status of the Lon device 4302 LonWorks 801 LonState Status of the Lon node 4302 LonWorks 802 LonBios Versione bios del modulo espansione LonWorks 3004 Expansion POL925 IO Input 1 X4 DIPOL687 ExFlow o...

Страница 61: ...cked and equipped with the suitable warning sign make sure no tension is present After switching the power off wait at least 5 minutes before accessing to the electrical panel or any other electrical...

Страница 62: ...power supply voltage vacuum and loaded X 16 absorption of the individual electric loads X 17 compressors carter heaters test X 18 leaks control 19 cooling circuit work parameters detection X 20 Safte...

Страница 63: ...er jet machine Keep the direction parallel to the flow of the flaps to avoid damages Check the aluminium flaps have not been damaged or folded on the contrary contact an authorised after sales assista...

Страница 64: ...d replacement of filters are very important from an hygienic sanitary point of view Operation with clogged filters leads to a reduction in the air flow rate with malfunctionings and block up to possib...

Страница 65: ...me that keeps the filters lifted from the tank base to have a settling bottom for the muds Remove the pre filter by lifting it of about 1 cm and remove it as shown in figure 1 Position the filter to b...

Страница 66: ...her wire stretching rod always by means of the curved beaks pliers Immerged electrodes humidifier Option Do not use solvents or detergents to clean the plastic components For descaling use a vinegar o...

Страница 67: ...e mounting it the filter body does not require replacing wash it with water and remount it on the new cylinder using the new gasket provided with the latter check the seal gasket between the cylinder...

Страница 68: ...area Professional electrical and electronic equipment must be disposed of by authorised personnel through established waste disposal authorities around the country In this regard here is the definiti...

Страница 69: ...ly check the positioning of the unit The installation of the unit in a place unsuited to support its weight and or guarantee adequate anchorage may result in consequent damage to things people or the...

Страница 70: ...t could be under voltage due to the start up of the unit may cause electric shocks burns and electrocution When voltage is necessary for the circuit open the isolator on the attachment line of the uni...

Страница 71: ...5 48 6 55 4 64 8 69 9 79 2 COP 1 4 68 4 66 4 68 4 54 4 60 4 66 4 62 4 42 Heating capacity EN14511 2018 13 kW 149 8 158 7 185 4 208 9 235 1 285 3 302 8 326 8 COP EN14511 2018 13 3 53 3 43 3 43 3 37 3...

Страница 72: ...99 95 98 88 84 75 70 67 72 92 54 4 101 95 95 90 87 78 74 72 72 92 60 4 105 95 95 91 86 80 75 73 72 93 70 4 106 96 95 92 88 83 77 75 73 94 80 4 106 97 96 93 89 82 77 75 74 95 90 4 107 101 100 94 92 85...

Страница 73: ...orrect operating and maintenance of the unit operating at full load To verify the operation field of the operating units with percentages of outdoor air always calculate the Tm mixing temperature at t...

Страница 74: ...sate drain 7 Functional spaces 8 Water heating coil inlet 1 1 2 9 Water heating coil outlet 1 1 2 10 Reheat coil optional 11 Treatment coil 12 water heating coil optional 13 F7 Electronic filters opti...

Страница 75: ...Dimensional drawings 75...

Страница 76: ...tal air supply AE Outdoor air intake CBK CCK CCKP version ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum c...

Страница 77: ...Dimensional drawings 77...

Страница 78: ...ply AE Outdoor air intake CBK CCK CCKP version ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WE...

Страница 79: ...Dimensional drawings 79...

Страница 80: ...ward air supply optional M5 Upflow air supply AE Outdoor air intake CBK CCK CCKP version ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mou...

Страница 81: ...Dimensional drawings 81...

Страница 82: ...with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 60 4 70 4 80 4 Configuration CAK CBK CCK CCKP CAK CBK CCK CCKP...

Страница 83: ...Dimensional drawings 83...

Страница 84: ...version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 60 4 70 4 80 4 Configuration CAK CBK CCK CCKP C...

Страница 85: ...Dimensional drawings 85...

Страница 86: ...air supply optional M5 Upflow air supply CBK CCK CCKP version AE Outdoor air intake ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount po...

Страница 87: ...Dimensional drawings 87...

Страница 88: ...with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 90 4 100 4 110 4 Configuration CAK CBK CCK CCKP CAK CBK CCK CCKP...

Страница 89: ...Dimensional drawings 89...

Страница 90: ...same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 90 4 100 4 110 4 Configuration CAK CBK CCK CCKP CAK CBK CCK CCKP CAK...

Страница 91: ...Dimensional drawings 91...

Страница 92: ...ra 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it FOR OVER 30 YEARS WE HAVE BEEN OFFERING SOLUTIONS TO ENSURE SUSTAINABLE COMFORT AND THE WELL BEING OF PEOPLE AND THE ENVIRON...

Отзывы: