Project: CL-10088-SM-REV-C
Client: Clenergy Australia
PV-ezRack
Engineering Certificate
ER-R-ECO (ECO Rail)
ER-I-05 (Tin Interface)
2 m x 1 m
3
1.5 mm
A
B
C
D
H < 5
5 < H < 10
10 < H < 15
15 < H < 20
20 < H < 30
PV ez-Rack SolarRoof Interface spacing Table for Tin Roof
Type of Rail
Type of Interface
Solar Panel Dimension
Terrain Category
Wind
Region
Building Height (m)
1074
1065
918
826
661
652
588
514
1671
1662
1597
1524
1441
1423
1368
1248
Note: The above spacings are for Up Wind End and Down Wind End Zone. Refer to Note 20 for Central
Zone spacings (10% increase).
Roof Angle - 30° <
α
< 60°
725
450
1377
1102
Purlin Thickness
Note: This Engineering report is based on 2 m x 1 m panels and two rails per panel. Refer to Note 12 for
further details.
Final Copy
11/12/2019