Installation Instruction
5.2.3 Adjust the vertical and horizontal
positioning using the long hole in the Roof
Hook and the loosely connected Z Module in
the rail, as shown in the figure on the right. The
roof hook should not protrude over the rail after
the adjustment.
The recommended torque is 16 ~20Nm.
5.3 PV Module Installation
5.3.1 Deployment of Grounding Clips
1) When there is an even number of PV Module
in each row:
Install the grounding clips at the positions
marked X in the figure shown. Then the number
of Grounding Clips = number of PV Module.
Eg; 4 grounding clips in the figure shown.
2) When there is an odd number of PV Module
in each row:
Install grounding clips at positions marked X in
figure shown.
Then the number of Grounding Clips = number
of PV 1. Eg; 6 grounding clips in
figure shown.
Please note:
When replacing a defective PV Module, it is
required to replace the grounding clip under
the defective PV Module.
5.3.2 Before installing the PV modules on
horizontal rail installations, add anti-slip
protection to the lowest row of PV modules.
To do this, fasten M6 x 20 mm bolts (with the
shank downwards) to the lower mounting holes
of the PV module frame. When installing large
modules (e.g. ASE250) M8 x 20 mm bolts must
be used.
±19mm