Appendix E
Falcon Lead Lag
E-53
If the setpoint source is
S2 4-20mA
then the setpoint is determined by
the 4-20mA input on S2, and the two param-
eters described below. If the 4-20mA signal goes out of range or is invalid, and this persists for a specified time,
then the setpoint source reverts to "Local". In this case once it has gone to
"Local", it remains that way until the 4-
20mA signal is stable again.
LL CH 20MA WATER TEMPERATURE: TEMPERATURE OR NONE
CH 4MA WATER TEMPERATURE: TEMPERATURE OR NONE
These provide the 20mA and 4mA temperatures for the interpolation curve. If either of these have the None value,
are invalid, are out of range, or are too close for interpolation, an alert is issued and the setpoint reverts to "Local"
when it is selected as 4-20mA.
LL CH SETPOINT: DEGREES OR NONE
This setpoint is used when the time-of-day input is off. If the ODR function is inactive then the setpoint is used as-is.
If the ODR function is active then this setpoint provides one coordinate for the outdoor reset curve.
LL CH TOD SETPOINT: DEGREES OR NONE
This setpoint is used when the time-of-day input is on. If the ODR function is inactive then the setpoint is used as-is.
If the ODR function is active then this setpoint provides one coordinate for the shifted (because TOD is on) outdoor
reset curve.
TIME OF DAY
The Time of Day has one sources of control: a switch contact. Closed TOD is an on condition; open, then TOD is
off.
OUTDOOR RESET AND BOOST (BOOST IS FUTURE)
The outdoor reset and boost functions for the LL CH functions will be implemented as described for a stand-alone
CH loop.
Each of the loops which implements outdoor reset and boost has its own parameters. The parameters used by the
LL master are:
•
LL setpoint
•
LL CH TOD Setpoint
•
LL Outdoor reset enable:
Disable, enable
•
LL CH ODR minimum outdoor
degrees or None
•
temperature:
•
LL CH ODR maximum outdoor
degrees or None
temperature:
•
LL CH ODR low water temperature: degrees or None
•
LL CH ODR boost time:
mm:ss or None
•
LL CH ODR boost max setpoint:
degrees or None
•
LL CH ODR boost step:
degrees or None
•
LL CH ODR boost recovery step time:mm:ss or None
The outdoor reset function requires the outdoor temperature. This temperature may be obtained from either a local
sensor or a LL slave as described earlier.
If the outdoor temperature is invalid and unknown, then no outdoor reset
action occurs and an alert is issued indicating an invalid outdoor temperature.
LL CH ODR MINIMUM WATER TEMPERATURE: DEGREES OR NONE
This specifies the minimum outdoor reset setpoint for the LL master. If the outdoor reset function calculates a tem-
perature that is below the temperature specified here, then this parameter's temperature will be used.
If this parameter is invalid or None then the outdoor reset function will be inhibited and will not run: if it is enabled
then an alert is issued.
Содержание ClearFire CFLC Series
Страница 6: ...vi...
Страница 14: ...Section 1 Introduction 1 8 Part No 750 363...
Страница 16: ...Section 2 Installation 2 2 Part No 750 363...
Страница 36: ...Section 2 Installation 2 22 Part No 750 363 Figure 2 13 Electrical Connections CFLC FALCON...
Страница 38: ...Section 2 Installation 2 24 Part No 750 363...
Страница 56: ...Section 3 Stack and Intake Vent Sizing and Installation 3 18 Part No 750 363...
Страница 87: ...Section 6 Parts Part No 750 363 6 3 Figure 6 1 Boiler Mechanical Assembly CFLC 4000 5000...
Страница 88: ...Section 6 Parts 6 4 Part No 750 363 Figure 6 2 Boiler Mechanical Assembly CFLC 6000 8000...
Страница 90: ...Section 6 Parts 6 6 Part No 750 363 Figure 6 4 Burner Assembly CFLC 4000 5000 UV SCANNER SEE FIGURE 6 7...
Страница 91: ...Section 6 Parts Part No 750 363 6 7 Figure 6 5 Burner Assembly CFLC 6000 8000 UV SCANNER SEE FIGURE 6 7...
Страница 95: ...Section 6 Parts Part No 750 363 6 11 Figure 6 10 Gas Train CFLC 6000 8000 optional 9 PPM NOx...
Страница 97: ...Section 6 Parts Part No 750 363 6 13 Figure 6 12 Gas train CFLC 10000 12000 optional 9 PPM NOx...
Страница 98: ...Section 6 Parts 6 14 Part No 750 363 Figure 6 13 Gas Train CFLC 4000 5000 Propane...
Страница 99: ...Section 6 Parts Part No 750 363 6 15 Figure 6 14 Gas Train CFLC 6000 8000 Propane...
Страница 100: ...Section 6 Parts 6 16 Part No 750 363 Figure 6 15 Gas Train CFLC 10000 12000 Propane...
Страница 105: ...Section 6 Parts Part No 750 363 6 21 Figure 6 20 Control Panel...
Страница 106: ...Section 6 Parts 6 22 Part No 750 363 Figure 6 21 Cables and Cable Harness...
Страница 108: ...Section 6 Parts 6 24 Part No 750 363 Figure 6 23 Casing Insulation 4000 5000 cont d...
Страница 109: ...Section 6 Parts Part No 750 363 6 25 Figure 6 24 Casing Insulation 6000 8000...
Страница 110: ...Section 6 Parts 6 26 Part No 750 363 Figure 6 25 Casing Insulation 6000 8000 cont d...
Страница 115: ...APPENDIX A Falcon Parameters...
Страница 116: ......
Страница 123: ...APPENDIX B Variable Speed Drive Parameters Sections B 1 B 5 PowerFlex 400 Sections B 6 B 8 PowerFlex 525...
Страница 124: ......
Страница 144: ......
Страница 145: ...APPENDIX C Gas Valve Page C 3 Siemens Gas Valve Page C 25 Dungs Gas Valve CFLC 4000 5000...
Страница 146: ......
Страница 147: ...Appendix C Gas Valve C 3...
Страница 148: ...Gas Valve Appendix C C 4...
Страница 149: ...Appendix C Gas Valve C 5...
Страница 150: ...Gas Valve Appendix C C 6...
Страница 151: ...Appendix C Gas Valve C 7...
Страница 152: ...Gas Valve Appendix C C 8...
Страница 153: ...Appendix C Gas Valve C 9...
Страница 154: ...Gas Valve Appendix C C 10...
Страница 155: ...Appendix C Gas Valve C 11...
Страница 156: ...Gas Valve Appendix C C 12...
Страница 157: ...Appendix C Gas Valve C 13...
Страница 158: ...Gas Valve Appendix C C 14...
Страница 159: ...Appendix C Gas Valve C 15...
Страница 160: ...Gas Valve Appendix C C 16...
Страница 161: ...Appendix C Gas Valve C 17...
Страница 162: ...Gas Valve Appendix C C 18...
Страница 163: ...Appendix C Gas Valve C 19...
Страница 164: ...Gas Valve Appendix C C 20...
Страница 165: ...Appendix C Gas Valve C 21...
Страница 166: ...Gas Valve Appendix C C 22...
Страница 167: ...Appendix C Gas Valve C 23...
Страница 168: ...Appendix C Gas Valve C 24...
Страница 186: ...Appendix C Gas Valve C 42...
Страница 187: ...APPENDIX D Falcon Alert Hold and Lockout Codes...
Страница 188: ......
Страница 208: ......
Страница 210: ......
Страница 230: ...Falcon Lead Lag Appendix E E 22 Figure 10 Falcon Lead Lag with outdoor reset and EMS for remote enable...
Страница 231: ...Appendix E Falcon Lead Lag E 23 Figure 11 Falcon LL with EMS for remote enable remote setpoint...
Страница 232: ...Falcon Lead Lag Appendix E E 24 Figure 12 Falcon Lead Lag with EMS for remote comms monitoring...
Страница 244: ...Falcon Lead Lag Appendix E E 36 13 Boiler Wiring Diagrams Model CFC ClearFire condensing boiler...
Страница 245: ...Appendix E Falcon Lead Lag E 37 Model CFW ClearFire hydronic boiler...
Страница 282: ......
Страница 283: ...APPENDIX F Falcon Program Module...
Страница 284: ......
Страница 285: ...Appendix F Program Module F 3...
Страница 286: ...Program Module Appendix F F 4...
Страница 287: ...Appendix F Program Module F 5...
Страница 288: ...Program Module Appendix F F 6...
Страница 289: ......
Страница 290: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...