Appendix E
Falcon Lead Lag
E-15
Modulation sensor
(steam) - choices are
S1 (J8-4)
and
S2 (J8-6).
Default is
S2
, the system header
pressure transmitter. In the event of a header pressure transmitter failure, the local transmitter (
S1
)
can be configured as the lead lag modulation sensor.
Note that in steam systems the modulation backup source must be manually configured. In hydronic
systems this selection will be made automatically based on the settings in
Modulation backup
sensor
above.
On, Off hysteresis
- The LL hysteresis values apply to all setpoint sources. The behavior of the
hysteresis function is identical to the behavior of the stand-alone hysteresis function, except:
• Where stand-alone hysteresis uses the on/off status of a single boiler, the LL hysteresis
uses the on/off status of all slave boilers: this status is true if any slave boiler is on, and
false only if all are off.
• Where stand-alone hysteresis uses time of turn-on and turn-off of a single boiler, the LL
hysteresis uses the turn-on of the first slave boiler and the turn-off of the last slave boiler.
PID gain
- The behavior of the lead lag PID function is identical to the behavior of the stand-alone
PID function. The same gain scalers and algorithms are used.
Demand Switch
- Selects the input for CH (steam) demand. If set to
Disable
, the LL master does
not respond to a demand.
Setpoint Source
- Selectable between
Local
and
S2 4-20mA
for remote setpoint operation (hot
water only; see
6.4
above).
4mA/20mA Water Temperature
(hot water only) - Defines the temperature range if
S2 4-20mA
selected as setpoint source.
Outdoor Reset
(hot water only) if enabled uses the current outdoor temperature to determine
setpoint (outdoor temperature sensor required; see
7.5
and
7.6
below).
Frost Protection
(hot water only) is active when enabled and outdoor temperature is below the
Outdoor frost protection setpoint.
If any slave indicates frost protection required, the Master will
turn on any pumps that are enabled for frost protection, and may additionally fire the current lead
burner at the
Frost protection rate
.
Lead lag selection method
and
rotation time
together determine the sequence order of boilers.
Base load common
- This is the firing rate threshold used for adding stages. If set to zero, this
parameter is disabled.
As demand increases, until all boilers are firing none will be requested to exceed the base load
common rate. Similarly, as demand decreases no boilers will be dropped until the load can be met
by remaining boilers firing at or below the base load rate.
The staging parameters (
Add/Drop stage method
,
detection time
, and
interstage delay
;
error
threshold, rate offset
) together determine, based on demand, when a boiler in the sequence will be
requested to turn on or off.
7.2 - Lead Lag Slave Configuration
It will be convenient to remain at the Master host boiler to configure the unit as a Slave (recall that
the lead lag Master is a communication function and not a separate controller - the Falcon hosting
the Master must also be configured as a Slave in order to be available to the lead lag network).
1. Go to CONFIGURE>Lead Lag Slave Configuration.
2. Available parameters are shown in Table 3. Make any necessary changes at this time.
Содержание ClearFire CFLC Series
Страница 6: ...vi...
Страница 14: ...Section 1 Introduction 1 8 Part No 750 363...
Страница 16: ...Section 2 Installation 2 2 Part No 750 363...
Страница 36: ...Section 2 Installation 2 22 Part No 750 363 Figure 2 13 Electrical Connections CFLC FALCON...
Страница 38: ...Section 2 Installation 2 24 Part No 750 363...
Страница 56: ...Section 3 Stack and Intake Vent Sizing and Installation 3 18 Part No 750 363...
Страница 87: ...Section 6 Parts Part No 750 363 6 3 Figure 6 1 Boiler Mechanical Assembly CFLC 4000 5000...
Страница 88: ...Section 6 Parts 6 4 Part No 750 363 Figure 6 2 Boiler Mechanical Assembly CFLC 6000 8000...
Страница 90: ...Section 6 Parts 6 6 Part No 750 363 Figure 6 4 Burner Assembly CFLC 4000 5000 UV SCANNER SEE FIGURE 6 7...
Страница 91: ...Section 6 Parts Part No 750 363 6 7 Figure 6 5 Burner Assembly CFLC 6000 8000 UV SCANNER SEE FIGURE 6 7...
Страница 95: ...Section 6 Parts Part No 750 363 6 11 Figure 6 10 Gas Train CFLC 6000 8000 optional 9 PPM NOx...
Страница 97: ...Section 6 Parts Part No 750 363 6 13 Figure 6 12 Gas train CFLC 10000 12000 optional 9 PPM NOx...
Страница 98: ...Section 6 Parts 6 14 Part No 750 363 Figure 6 13 Gas Train CFLC 4000 5000 Propane...
Страница 99: ...Section 6 Parts Part No 750 363 6 15 Figure 6 14 Gas Train CFLC 6000 8000 Propane...
Страница 100: ...Section 6 Parts 6 16 Part No 750 363 Figure 6 15 Gas Train CFLC 10000 12000 Propane...
Страница 105: ...Section 6 Parts Part No 750 363 6 21 Figure 6 20 Control Panel...
Страница 106: ...Section 6 Parts 6 22 Part No 750 363 Figure 6 21 Cables and Cable Harness...
Страница 108: ...Section 6 Parts 6 24 Part No 750 363 Figure 6 23 Casing Insulation 4000 5000 cont d...
Страница 109: ...Section 6 Parts Part No 750 363 6 25 Figure 6 24 Casing Insulation 6000 8000...
Страница 110: ...Section 6 Parts 6 26 Part No 750 363 Figure 6 25 Casing Insulation 6000 8000 cont d...
Страница 115: ...APPENDIX A Falcon Parameters...
Страница 116: ......
Страница 123: ...APPENDIX B Variable Speed Drive Parameters Sections B 1 B 5 PowerFlex 400 Sections B 6 B 8 PowerFlex 525...
Страница 124: ......
Страница 144: ......
Страница 145: ...APPENDIX C Gas Valve Page C 3 Siemens Gas Valve Page C 25 Dungs Gas Valve CFLC 4000 5000...
Страница 146: ......
Страница 147: ...Appendix C Gas Valve C 3...
Страница 148: ...Gas Valve Appendix C C 4...
Страница 149: ...Appendix C Gas Valve C 5...
Страница 150: ...Gas Valve Appendix C C 6...
Страница 151: ...Appendix C Gas Valve C 7...
Страница 152: ...Gas Valve Appendix C C 8...
Страница 153: ...Appendix C Gas Valve C 9...
Страница 154: ...Gas Valve Appendix C C 10...
Страница 155: ...Appendix C Gas Valve C 11...
Страница 156: ...Gas Valve Appendix C C 12...
Страница 157: ...Appendix C Gas Valve C 13...
Страница 158: ...Gas Valve Appendix C C 14...
Страница 159: ...Appendix C Gas Valve C 15...
Страница 160: ...Gas Valve Appendix C C 16...
Страница 161: ...Appendix C Gas Valve C 17...
Страница 162: ...Gas Valve Appendix C C 18...
Страница 163: ...Appendix C Gas Valve C 19...
Страница 164: ...Gas Valve Appendix C C 20...
Страница 165: ...Appendix C Gas Valve C 21...
Страница 166: ...Gas Valve Appendix C C 22...
Страница 167: ...Appendix C Gas Valve C 23...
Страница 168: ...Appendix C Gas Valve C 24...
Страница 186: ...Appendix C Gas Valve C 42...
Страница 187: ...APPENDIX D Falcon Alert Hold and Lockout Codes...
Страница 188: ......
Страница 208: ......
Страница 210: ......
Страница 230: ...Falcon Lead Lag Appendix E E 22 Figure 10 Falcon Lead Lag with outdoor reset and EMS for remote enable...
Страница 231: ...Appendix E Falcon Lead Lag E 23 Figure 11 Falcon LL with EMS for remote enable remote setpoint...
Страница 232: ...Falcon Lead Lag Appendix E E 24 Figure 12 Falcon Lead Lag with EMS for remote comms monitoring...
Страница 244: ...Falcon Lead Lag Appendix E E 36 13 Boiler Wiring Diagrams Model CFC ClearFire condensing boiler...
Страница 245: ...Appendix E Falcon Lead Lag E 37 Model CFW ClearFire hydronic boiler...
Страница 282: ......
Страница 283: ...APPENDIX F Falcon Program Module...
Страница 284: ......
Страница 285: ...Appendix F Program Module F 3...
Страница 286: ...Program Module Appendix F F 4...
Страница 287: ...Appendix F Program Module F 5...
Страница 288: ...Program Module Appendix F F 6...
Страница 289: ......
Страница 290: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...