Install anchors into the floor. Replace raised floor panels and
insert threaded rods through the four holes.
Note:
You are not installing the rods at this point. We are
measuring the rods to be cut to the appropriate length.
Measure the rods 2.5” above the floor and mark with a
permanent marker. Remove the rods and cut each rod at the
mark. Remove the floor panels.
Before installing rods back into the floor, place a nut and then
a washer on the threaded rods. Take the rod and install it into
the anchor installed in the floor.
Tighten the nut down to secure the rod into the floor. Tighten
each bolt to 65 ft-lbs., +10, -0 ft-lbs. The anchor will expand
and secure itself to the floor.
Once all four rods are secure, thread another hex nut, then
washer on each rod. Make sure the nut and washer are
approximately ½” below the raised floor level. This hardware
will be tightened down AFTER the frame is set into place but
BEFORE securely bolting the frame to the floor.