1-3
1-5 Major functions
This unit provides various functions. For details of setting and operation, refer to each item No.
Functions Items
Contents
Page
No.
1. Digital display
①
Measuring data display
Measuring data in each channel are displayed.
Channel No. (3 digits) + tag (8 digits) + range (3 digits) + measured value (7 digits)
An 8-digit tag can be set and displayed.
In case of collective display of 36 points, 5-digit display is done by justifying left
digits.
A unit can also be displayed instead of the tag, and its display mode is the same
as in the tag. (Simultaneous display of both tag and unit cannot be done.)
Page 2-2
②
Display mode
1) Each measuring data is fixed or sequentially displayed every channel.
2) 12-point measuring data are displayed collectively.
3) 24-point measuring data are displayed collectively.
4) 36-point measuring data are displayed collectively.
※
The update cycle of 1 channel display is 2 seconds as a factory delivery value
(default).
5) In case of 24 or 36 input points, each measuring data is fixed or sequentially
displayed every 12 points.
※
The update cycle of 12
・
24
・
36 points display is 3 seconds as a factory delivery
value (default).
6) The type code, serial No., and version No. of software of this unit are indicated.
The chart speed, date (year, month, day), and time are indicated at all times
in all display modes 1) - 6).
Page 2-2
③
Status display
1) KEY LOCK : Indicated when operation keys are locked.
2) CHART END : Indicated when the chart comes to an end.
3) FAIL
: Indicated when the unit is in trouble.
Page 2-1
Page 2-2
④
Alarm status display
1) Measuring data in an alarm channel are displayed red.
※
Red ALM LED flickers.
Page 2-1
Page 2-2
⑤
Setting data display
Setting conditions can be confirmed by displaying various parameters by means
of key operation.
Page 8-1
2. Analog
recording
①
No. of recording points
Setting inputs and arithmetic results can be recorded by max. 36 channels,
respectively.
Page 8-10
②
Recording color
designation
A recording color can be designated optionally every channel (out of 10 colors).
Page 8-10
③
Tag number printing
Tag numbers (channel numbers) are printed beside the trend recording at a fixed
interval.
-
④
Scale and unit printing
A scale and a unit are printed at both ends of the chart every fixed time.
-
⑤
Alarm mark printing
When an alarm occurred or when the alarm was reset, _ (red) or
_ (
green) mark is
printed beside the trend recording, and also, the time, channel number, and kinds
of levels are printed at the right end of the chart.
-
⑥
Skip function
A designated channel can be skipped.
Page 8-10
⑦
Analog recording format
(option)
Parallel recording, partially compressed/enlarged recording, and automatic range
selection recording can be selected.
-
3. Digital
recording
①
Data interval recording
Digital recording is done at an optional interval (time and minute) from a
designated start time by overlapping it with analog recording.
Page 8-21
②
Data printing
Digital recording is done at the requested time while interrupting analog recording.
Page 6-2
③
Logging recording
Digital recording is done at an optional interval (time and minute) from a
designated start time.
Page 8-22
④
Digital recording format
Measuring data, tag number, unit, chart speed, date (year, month, day), and time
are printed. Three kinds of recording formats can be designated optionally.
Page 8-21
Page 8-23
⑤
Skip function
A designated channel can be skipped.
Page 8-8
4. Arithmetic
results
recording
①
Differential recording
1) A difference of measuring data between designated channels is recorded in an
optional designated channel.
2) A difference between measuring data of a designated channel and the
reference value (optional setting) can be recorded in an optional designated
channel.
Page 8-16
②
Arithmetic results
recording (option)
1) The maximum, minimum, average, and total values of measuring data between
designated channels are recorded in an optionally designated channel.
2) A time series change (maximum, minimum, average, and integration) at an
optional interval of measuring data between designated channels can be
recorded in an optional channel from a designated start time.