13-13
2
.
Inter-channel
1)
Refer to setting of differential recording and set it.
(Ⅰ.
Instruction manual
8-7.「CALC.」 )
2)
Select [MIN], [MAX], [AVE], or [SUM] for kind.
3)
Refer to previous page [1. Differential operation] for screen of setting list display (collective 12 point)
Unrelated items for type which is set in operation output channel is not displayed.
4)
Refer to previous page [1. Differential operation] for display of setting parameter recording.
The cursor dose not move to parameter input area of unnecessary setting depending on set operation type.
Select one from following for operation type of inter-channel.
MIN
Inter-CH minimum value
MAX
Inter-CH maximum value
AVE
Inter-CH average value
SUM
Inter-CH
sum
value
CH
5)
Refer to below for selecting of inter-channel.
①
[None]: Only 1channel is selected.
②
[/]: 2 channels which are channel
○○
and channel
○○
are selected.
③
[
~
]: Several channels which are from channel
○○
to channel
○○
are selected.
【
Example
】
When select 9 channels which are channel 1,2,3,4,5,6,7,8, and 12, setting like below.
1 ~ 8 / 12
3
.
Time series
1)
Refer to setting of differential recording and set it.
(Ⅰ.
Instruction manual
8-7.「CALC.」 )
2)
Select [TMIN], [TMAX], [TAVE], or [TSUM] for kind.
3)
Refer to previous page [1. Differential operation] for screen of setting list display (collective 12 point)
Unrelated items for type which is set in operation output channel is not display.
4)
Refer to previous page [1. Differential operation] for display of setting parameter recording.
The cursor dose not move to parameter input area of unnecessary setting depending on set operation type.
Select one from following for operation type of time series.
TMIN
Minimum value every interval
TMAX
Maximum value every interval
TAVE
Average value every interval
TSUM
Totalizing value every interval
5)
Refer to following for start time and interval.
①
Setting of start time is from
00 : 00
to
23 : 59
and optional setting by every 1
minute.
②
Setting of interval is from
00 : 01
to
24 : 59
and optional setting by every 1
minute.
(Note 1)
When input type of operation output channel is [unused], do not record and display even if detail setting of
operation is done.
(Note 2)
In case of minimum value operation, when there are [under flow]/[under range] in the data which is
specified channel, minimum value is [under flow] or [under range]. However, when retuned to normal
data, error data is deleted from operation data. (same as maximum vale and average value operation).
(Note 3)
In case of time series operation, not recording before set start time.
(Note 4)
When there are error data such as [over], [under], and [burnout] in time series operation, do like (Note 2).
(Note 5)
When power is off after set start time in time series operation, data during that time is deleted from
operation result.