RIM-600 Manual
36
an RJ-45 interconnect cable to connect the RIM-600 Node to the patch panel in room A, and an RJ-
45 interconnect cable from the wall jack in room B to the sensor.
The sensor produces an analog signal which must connect directly to the Host or Node.
The path from the sensor to the RIM-600 unit CANNOT pass through a network Hub or
Switch.
Network Configuration
The RIM-600 Node has a serial port on the front panel which is used to configure network settings
and security options. A dumb terminal or terminal emulation software is required to get online and
set up the configuration. The port is male DTE, so a DB9 female–female null modem cable will be
required. Terminal communication settings must be set to:
n
9600 baud, no parity, 8 data bits, 1 stop bit, no flow control
To get online with the RIM-600 Node, connect your terminal to the serial port and press
<RETURN>.
A menu will appear which will guide you through the setup.
RIM-600 Node Unit Version: 4.10
Main Menu
1. Display Network configuration
2. Configure Network settings
3. Display system statistics
4. Reset to factory defaults
5. Network Debug
6. Reboot
7. Logout
Enter option->
To display the present Network Configuration settings select
Option 1
. To program the Network
settings select
Option 2
. Note that the Node must have network visibility of the Host for the
RIM-600 system to function properly. For Network changes to take effect you must reboot the unit
(option 5). A typical sample is shown below:
Network Configuration
Physical Address
00:07:F9:00:10:18
Parent Host IP address
10.1.2.47
Node IP Address
10.1.4.17
Subnet Mask
255.255.255.0
Default Gateway
10.1.4.1
DNS Server
10.1.2.111
Node name
48th Floor Chicago
Allow remote configuration N
Press any key to return to main menu