Emotron VS Series Quick Start Guide
- 117 -
0
Cut-off frequency of
torque boost
Torque boost
Output frequency
(
Hz)
Output voltage (V)
Rated voltage of motor
Rated frequency of motor
Fig 6-25 Torque boost
d1.03
Multi-point V/F frequency 1(F1)
Range:0.0
~
d1.05
Default:0.0Hz
d1.04
Multi-point V/F voltage 1(V1)
Range:0.0
~
100.0%
Default:0.0%
d1.05
Multi-point V/F frequency 2(F2)
Range:d1.03
~
d1.07
Default:5.0Hz
d1.06
Multi-point V/F voltage 2(V2)
Range:0.0
~
100.0%
Default:14.0%
d1.07
Multi-point V/F frequency 3(F3)
Range:d1.05
~
d1.09
Default:25.0Hz
d1.08
Multi-point V/F voltage 3(V3)
Range:0.0
~
100.0%
Default:50.0%
d1.09
Multi-point V/F frequency 4(F4)
Range:d1.07
~
rated motor
frequency
Default:50.0Hz
d1.10
Multi-point V/F voltage 4(V4)
Range:0.0
~
100.0%
Default:100.0%
d1.03
~
d1.10 is used for broken line V/f mode. Voltage value 100% corresponds to rated voltage
of motor. Please rationally set the values of frequency and voltage at knees on the basis of
characteristics of motor and load. Improper setting may rise output current even burn the motor. Figure
6-26 setting of multi-point V/F curve.
0
F1
F2
F3
F4
V1
V2
V3
V4
Output voltage (V)
Rated voltage of motor
Output frequency
(
Hz)
Rated frequency of motor
Fig 6-26
ATTENTION:
The multi-point V/F curve is set based on the motor's load characteristic. The relationship
between voltages and frequencies is:V1≤V2≤V3≤V4
,
F1≤F2≤F3≤F4.At low frequency, higher voltage
may cause overheat or even burnt out of the motor and overcurrent stall or overcurrent protection of
the AC drive.