Emotron VS Series Quick Start Guide
- 152 -
5). MPPT voltage range
y0.04 and y0.05 are respectively the lowest voltage and highest voltage under the MPPT mode.
Smaller the range between the two, the faster is the tracing of maximum power, but the bus voltage
during normal operation must fall within this range else the maximum power point may not be tracked.
Generally, the factory default value is OK.
6). Setting of fault point and fault delay reset time
If clients need to use the pre-warning of weak light, water-logged, under-load, failure monitoring point,
delay time and reset time, water-logged/controlled function can be set as y0.15~y0.19 on demand;
under-load function can be set as y0.20~y0.22; weak light function as y0.13~y0.14. Users can also go
for the default values.
7). Parameter setting after the system’s normal operation
When the water yield is normal, and system is running steadily, the commissioning is completed. And
then set b1.00=1, to change the terminal operation mode. Set auto reset times, E0.27=5 (as per
system requirement).
◆
B: Grid or Generator power supply wiring
Refer wiring drawing of inverter as shown in Figure 7-4
Q1
R/L1
S/L2
T/L3
GND
DI1
DI2
DI3
DI4
DI5
DI6
+10V
AI1
AI2
GND
PE
U/T1
V/T2
W/T3
485+
485-
GND
R1A
R1B
R1C
Q2
M
(-)
(+)
PB
VSR
Y2/HO
PLC
DI7/HI
+24V
AI3
AO1
GND
+24V
Y1
AO2
GND
R2A
R2B
R2C
PV panels
Grid or
generator set
PV Voltage
Given selection
Operation panel
Tank
The water
level sensor
RUN/STOP
Fig 7-4 Grid or Generator Power Supply Wiring Diagram
1) Refer Figure 7-4 and ensure wiring is done as per the connection done in this figure.