Emotron VS Series Quick Start Guide
- 126 -
E0.25
Decel time at
instantaneous power failure
Range: 0.0
~
6000.0s
Default: 5.0s
E0.30
Instantaneous power off
bus voltage
Range: 60.0%
~
E0.31
Default: 80.0%
E0.31
Instantaneous power off
recovery voltage
Range: E0.30
~
100.0%
Default: 85.0%
E0.32
Instantaneous power off
voltage judge time
Range: 0.00
~
10.00s
Default: 0.10s
E0.33
Instantaneous power off
gain Kp
Range: 0.1
~
100.0%
Default: 40.0%
E0.34
Instantaneous integration time
Ti
Range: 0.00
~
10.00s(0.00:
Integration invalid)
Default: 0.10s
Notice:
1. Proper adjustment of E0.25, can avoid production stop due tothe protection of the inverter
when power switch
2. Input phase lack protection function must be forbidden to enable this feature
E0.26
Rapid current limit
Range: 0
~
1
Default: 0
0: Disabled
1: Enabled
The rapid current limit function can reduce the AC drive's overcurrent faults at maximum,
guaranteeing uninterrupted running of the AC drive. However, long-time rapid current limit may cause
the AC drive to overheat, which is not allowed. In this case, the AC drive will report Err26, indicating
the AC drive is overloaded and needs to stop
E0.27
Times of automatic trip(fault )
reset
Range:0
~
20
Default: 0
It is used to set the times of fault auto resets if this function is used. After the value is exceeded,
the AC drive will remain in the fault state.
E0.28
Interval of automatic trip(fault)
reset
Range:0.1
~
100.0s
Default:1.0s
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
E0.29
DO action during fault auto
reset
Range:0
~
1
Default: 0
0: Not act
1: Act
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset function is
selected.
E0.35
The type of motor temperature
sensor
(VSX Only)
Range: 0
~
2
Default: 0
0:None
1:PT100
2:PT1000
E0.36
Select which port as the supply
of the motor temperature
sensor
(VSX Only)
Range: 0
~
2
Default: 0
0:None
1:AO1
Select AO1 as the power input of motor temperature sensor
2:AO2
Select AO2 as the power input of motor temperature sensor