Emotron VS Series Quick Start Guide
- 158 -
y0.05(Brake Open Frequency (Rising))
、
y0.06(Brake Release Frequency (Rising)) and
y0.07(Brake Open Frequency (Falling))
、
y0.08(Brake Release Frequency (Falling)) are same
meanings, rising group use for frequency adjusting on FWD, falling group use for frequency adjusting
on REV.
y0.11
Brake Open Type
0: Open according to frequency
Default: 0
1: Open according to frequency &
current
0
:
Open according to frequency
Criteria for judging the brake opening is inverters output reach to the setting frequency of Y0.05
(rising) or y0.07 (falling), and then open the brake by setting time of y0.01 (Brake Open Delay).
1: Open according to frequency and current
Criteria for judging the brake opening is inverters output reach to the setting frequency of y0.05
(rising) or y0.07 (falling), meanwhile, inverter current reach y0.09 (brake open current) setting value.
y0.12
Emergency Operation
Frequency
0.00
~
50.00Hz
Default:
5.00Hz
When emergency signal input, inverters will entry emergency operating mode, the frequency of
y0.12 will be the operation frequency of inverter, and inverter will select accel/decel time 4 as current
accel/decel time.
y0.13
Maintenance Operation
Frequency
0.00
~
50.00Hz
Default:
8.00Hz
When maintenance signal input, the frequency of y0.13 will be the operation frequency of inverter
y0.14
Emergency Signal
Processing
0: Elevator no run
Default: 1
1: Elevator Powered on By UPS
And Run
0: 0: Elevator no run
When emergency signal input, inverter no output
1: Elevator Powered on By UPS And Run
When emergency signal input, inverter is powered by UPS and output via emergency operation
frequency
y0.18
Short Floor Function
0:Invalid
Default: 0
1:Short Floor Function
2:Senior Short Floor Function
0: Invalid
Short floor function is invalid
1: Short floor function
When elevator is running during short floor and when short floor function is triggered, inverter
will continue to run via setting speed of y0.19.
2
:
Senior short floor function
When elevator is running during short floor and when short floor function is triggered, inverter will
calculate remaining running time and maintain current frequency to run till remaining time finished
y0.19
Short Floor Speed
0.0
~
100.0%
Default:
60.0%
When y0.18=1, inverter run via speed of y0.19 when running in short floor
y0.20
Leveling Jerk
0.0~100.0%
Default:
0.0%
y0.21
Leveling Jerk Frequency
0.00~1.00
Default:
0.20
The parameters are used for improving the jerk when elevator stop
y0.22
Motor Mode Slip
0.00~3.00Hz
Default:
0.00Hz