Mounting
Electrical installation
Connection to the 400 V system
4.3.2.2
Fuses and cable cross-sections
Operation without mains choke
Cable installation in compliance with EN 60204-1
Laying system B2
Inverter
VS30401P3
VS30401P8
VS30402P4
VS30403P2
VS30403P9
VS30405P6
Rated power
kW
0.37
0.55
0.75
1.1
1.5
2.2
Rated mains current
without mains choke
A
1.8
2.5
3.3
4.4
5.4
7.8
Fuse
Fusing characteristics
gG/gL or gRL
Max. rated fuse current A
10
10
10
16
16
16
Cable cross-section
mm²
1.5
1.5
1.5
2.5
2.5
2.5
Circuit breaker
Fusing characteristics
B
Max. rated fuse current A
10
10
10
16
16
16
Cable cross-section
mm²
1.5
1.5
1.5
2.5
2.5
2.5
Earth-leakage circuit
breaker
≥ 30 mA, type
B