Technical data
6
23
Standards and operating conditions
6
Technical data
6.1
Standards and operating conditions
Conformities
CE
2014/35/EU
Low-Voltage Directive
2014/30/EU
EMC Directive (reference: CE-typical drive system)
EAC
TR TC 004/2011
Eurasian conformity: Safety of low voltage equipment
TP TC 020/2011
Eurasian conformity: Electromagnetic compatibility of
technical means
RoHS 2
2011/65/EU
Restrictions for the use of specific hazardous materials
in electric and electronic devices
Approvals
UL
UL 61800-5-1
for USA and Canada (requirements of CSA 22.2 No.
274)
Energy efficiency
Class IE2
EN 50598-2
Type of protection
IP20
EN 60529
Type 1
NEMA 250
Protection against contact
Open type
only for UL approved systems
Insulation resistance
Overvoltage category III
EN 61800-5-1
0 … 2000 m a.m.s.l.
Overvoltage category II
above 2000 m a.m.s.l.
Control circuit isolation
Safe mains isolation by double/
reinforced insulation
EN 61800-5-1
Protective measures against
Short circuit
Earth fault
Earth fault strength depends on the operating status
Overvoltage
Motor stalling
Motor overtemperature
I²xt monitoring
Leakage current
> 3.5 mA AC, > 10 mA DC
EN 61800-5-1
Observe regulations and safety instructions!
Mains switching
3-time mains switching in 1 min
cyclic, without restrictions
Starting current
≤ 3 x rated mains
current
Mains systems
TT
Voltage to earth/ground: max. 300 V
TN
IT
Apply the measures described for IT systems!
IT systems not relevant for UL approved systems
Operation on public supply systems
Implement measures to limit the radio
interference to be expected:
The compliance with the requirements for the
machine/plant is the responsibility of the
manufacturer of the machine or plant!
< 0.5 kW: with mains choke
EN 61000-3-2
0.5 ... 1 kW: With active filter
> 1 kW at mains current ≤ 16
A:
without additional measures
Mains current > 16 A: with mains
choke or mains filter, with
EN 61000-3-12
RSCE: Short-circuit power ratio at the connection
point of the machine/plant to the public network.
Содержание Emotron VS10 Series
Страница 1: ...Emotron VS10 VS30 AC drive 0 25 2 2 kW Mounting and switch on instruction ...
Страница 2: ...Diese Seite wurde absichtlich leer gelassen ...
Страница 10: ...10 4 Mounting Mechanical installation Dimensions VS10 VS30 0 55 kW 0 75 kW All dimensions in mm ...
Страница 11: ...11 Mounting Mechanical installation 4 Dimensions VS30 1 1 kW 2 2 kW All dimensions in mm ...