24
6
Technical data
Standards and operating conditions
dimensioning for rated power. Rsce
≥
120 is to be met.
Requirements to the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shield < 75/150
pF/m
≤ 2,5 mm² /
AWG 14
C-core-core/C-core-shield < 150/300
pF/m
≥ 4 mm² /
AWG 12
Electric strength
Uo/U = 0,6/1,0 kV
U = r.m.s. value external conductor/external
conductor
Uo = r.m.s. value external conductor to PE
U ≥ 600 V
UL
U = r.m.s. value external conductor/external
conductor
Climate
1K3 (-25 ... +60 °C)
EN 60721-3-1
Storage
2K3 (-25 ... +70 °C)
EN 60721-3-2
Transport
3K3 (-10 ... +55 °C)
EN 60721-3-3
Operation
Operation at a switching frequency of 8 or 16 kHz:
above +40°C, reduce rated output current by 2.5 %/°C
Site altitude
0 … 1000 m a.m.s.l.
1000 … 4000 m a.m.s.l.
Reduce rated output current by 5 %/1000 m
Pollution
Degree of pollution 2
EN 61800-5-1
Vibration resistance
Transport
2M2 (sine, shock)
EN 60721-3-2
Operation
Amplitude 1 mm
Germanischer Lloyd 5 ... 13.2 Hz
acceleration resistant up to 0.7 g
13.2 ... 100 Hz
Amplitude 0.075 mm
EN 61800-5-1
10 ... 57 Hz
acceleration resistant up to 1 g
57 ... 150 Hz
Noise emission
Category C2
EN 61800-3
type-dependent, for motor cable lengths see rated
data
Noise immunity
Meets requirement in compliance with EN 61800-3
Содержание Emotron VS10 Series
Страница 1: ...Emotron VS10 VS30 AC drive 0 25 2 2 kW Mounting and switch on instruction ...
Страница 2: ...Diese Seite wurde absichtlich leer gelassen ...
Страница 10: ...10 4 Mounting Mechanical installation Dimensions VS10 VS30 0 55 kW 0 75 kW All dimensions in mm ...
Страница 11: ...11 Mounting Mechanical installation 4 Dimensions VS30 1 1 kW 2 2 kW All dimensions in mm ...