13
Mounting
Electrical installation
Connection to the 230 V system
4
4.3.1.2
Fuses and cable cross-sections
Operation without mains choke
Cable installation in compliance with EN 60204-1
Laying system B2
Inverter
VS10231P7
VS10232P4
VS10233P2
VS10234P2
VS10236P0
VS10237P0
VS10239P6
Rated power
kW
0.25
0.37
0.55
0.75
1.1
1.5
2.2
Rated mains current
without mains choke
A
4
5.7
7.6
10
14.3
16.7
22.5
Fuse
Fusing characteristics
gG/gL or gRL
Max. rated fuse current A
10
10
16
16
25
25
25
Cable cross-section
mm²
1.5
1.5
2.5
2.5
6
6
6
Circuit breaker
Fusing characteristics
B
Max. rated fuse current A
10
10
16
16
25
25
25
Cable cross-section
mm²
1.5
1.5
2.5
2.5
6
6
6
Earth-leakage circuit
breaker
≥ 30
mA, type A or B