2.1 handling
The cabinet shall not be lifted using lifting eyes.
Remove weight from the cabinet by unplugging the inverters. mark inverters clearly with shelf and position for correct. This
is especially important in three phase configurations.
Empty inverter positions must not be left open. Replace with module or cover.
2.2 Surge and transients
The mains (AC) supply of the modular inverter system shall be fitted with suitable lightning surge suppression and Transient
voltage surge suppression for the application at hand. manufacturer’s recommendations of installation shall be adhered. It is
advisory to select device with alarm relay for function failure.
Indoor sites are considered to have a working lightning surge suppression device in service.
Indoor sites min Class II
outdoor sites min Class I + Class II or combined Class I+II
2.3 other
Isolation test must not be performed without instructions from the manufacturer.