![CE+T Power TSI Bravo Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/ce-t-power/tsi-bravo/tsi-bravo_user-manual_2577181027.webp)
9.4.6 Connection Table – AC Input (X2) +24DC
The AC input supply breaker shall be 2p (for single phase) and min 3p (for three phase)
power (kvA)
AC Input
Screw terminal
1ph
3ph
fuse/CB
Cable mm
2
6
32A
6
12
63A
16
18
100A
35
18
3x32A
3x6
24
125A
50
30
160A
70
36
200A
95
36
3x63A
3x16
42
225A
150
45
3x80A
3x25
48
250A
150
9.4.7 Connection Table – AC Input (X2) -48vDC to 220vDC
The AC input supply breaker shall be 2p (for single phase) and min 3p (for three phase)
power (kvA)
AC Input
Screw terminal
1ph
3ph
fuse/CB
Cable mm
2
6
40A
10
12
80A
25
18
125A
50
30
3x40A
3x10
40
160A
70
50
200A
95
60
240A
150
60
3x80A
3x25
70
280A
185
75
3x100A
3x35
80
320A
27