13. AC output distribution
13.1 miniature Circuit breaker installation/removal
Circuit breakers are normally installed from factory.
how to add breakers
1.
Insert the short connection cable (10mm2 (included)) in the breaker line-side and tighten.
- up to 50A breaker use one connection cable.
- 63A breaker use two connection cables.
2.
Clip breaker on to the DIn rail
3.
Insert Insulated screw driver in the terminal to load the spring
4.
Insert connection cable and remove screw driver
5.
Connect load cable to breaker, neutral and ground
6.
Switch breaker on
Remove breaker in reverse order
13.2 mCCB
mCCBs are installed from factory.
A wide range of breakers is used. Breakers in picture may be different upon delivery.
1.
make sure that the breaker is in off position
2.
Connect load cables to the terminal
3.
Switch the breaker on
37
– TSI Bravo – user manual – v7.0