![CE+T Power TSI Bravo Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/ce-t-power/tsi-bravo/tsi-bravo_user-manual_2577181032.webp)
10. Interface
10.1 Inverter module
=
~
=
=
=
~
AC out
DC in
AC in
Inverter Status
Output Power Status
Inverter Status lED
Description
Remedial action
off
no input power or forced stop
Check environment
permanent green
operation
Blinking green
Converter ok but working conditions are
not fulfilled to operate properly
Blinking green/orange alternatively
Recovery mode after boost
(10 In short circuit condition)
permanent orange
Starting mode
Blinking orange
modules cannot start
Check T2S
Blinking red
Recoverable fault
permanent red
non recoverable fault
Send module back for repair
output power (redundancy not counted)
<5%
5% to
40%
40 to
70%
80 to
95%
100%
100% =
overload
output power (redundancy not counted)
×
×
×
Status output power lED
×
×
×
1B
1p
2p
2p
3p
3B
Behavior (B = blinking – p permanent )
10.2 T2S
Alarm indication on T2S (urgent / non urgent / Configurable)
- green:
no alarm
- Red:
Alarm
- flashing Exchanging information with inverters (only Configurable alarm)
outgoing alarm relay delay
- urgent
60 seconds delay
- non urgent
30 second delay
parameter setting via laptop or Copy/paste.
factory default according to list of set values, see Table of set values
major Alarm
minor Alarm
user selectable Alamr
uSB port
32
– TSI Bravo – user manual – v7.0