![CE+T Power TSI Bravo Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/ce-t-power/tsi-bravo/tsi-bravo_user-manual_2577181020.webp)
8.2.9 Remote on/off
notice: The shelf is by default equipped with a connection between pin 3 and 2. If remote on/off is not used the strap shall
remain in all connected shelves. Should the remote on/off be used all straps must be removed and in one (1) shelf
replaced with a changeover contact or emergency button.
The remote on/off switch the output AC off.
Input AC and input DC is not affected by the remote on/off.
The remote on/off can be connected to any shelf.
The remote on/off requires changeover contacts, one input opens as the other close.
If both transitions are not picked up the status is not changed
Relay characteristics (Remote on/off)
Signal voltage
+5vDC (galvanic insulated)
max wire size
1mm2
functional table for remote on/off function
#
pin 1-3
pin 2-3
Status
Indication
1
open
open
normal operation
All (green)
2
Closed
open
off
AC output (off)
AC Input (green)
DC Input (green)
3
open
Closed
normal operation
All (green)
4
Closed
Closed
normal operation
All (green)
3
2
1
Common
ON
OFF
20