5.3 AC distribution unit
5.3.1 miniature circuit breakers
The standard AC output distribution is designed with
a 35mm DIn rail, multiClip termination board and n/pE
copper terminal bars and built as a part of the cabinet.
The multiClip offers a unique flexibility during
installation and expansion. The terminals are spring
loaded and adapts contact pressure to the size of
conductor. only one cable can be inserted per spring
loaded terminal.
The AC distribution unit comes as 1 pole, 2 pole and 3 pole
max current per AC Du is 200A, max current per terminal connector is 50A. Two adjacent terminal connectors shall be used for
63A breakers
If alarm is required for AC output breakers a held contact attached to each individual breaker is used (of or SD). The alarm
function is common and use one of the digital input on the control unit. The help contact limit the qty breakers
Single pole
Double pole
Three pole
w/o help
contact
With help
contact of/SD
w/o help
contact
With help
contact of/SD
w/o help
contact
With help
contact of/SD
up to 40A
24
16
12
9
8
6
5.3.2 mCCB
AC output distribution via mCCB in the range
up to 400A (1p, 2p or 3p)
max two mCCB per inverter cabinet.
13
– TSI Bravo – user manual – v7.0