8.2.2 Surge suppression
The mains (AC) supply of the modular inverter system shall be fitted with suitable lightning surge suppression and Transient
voltage surge suppression for the application at hand. manufacturer’s recommendations of installation shall be adhered. It is
advisory to select device with alarm relay for function failure.
Indoor sites are considered to have a working lightning surge suppression device in service.
Indoor sites min Class II
outdoor sites min Class I + Class II or combined Class I+II
8.2.3 Terminations
All terminations are clearly marked.
8.2.4 grounding
“pE ChASSIS gRounD”
pE Chassis ground shall be wired to mET or distributed earth bar connected to mET
According to local regulations.
8.2.5 DC input
CB per inverter module
Cable, min
Connector
Torque
+24vDC
80A
2 x 25mm
2
m5
1.5nm
-48vDC / Bravo pack
63A
2 x 16mm
2
-60vDC
50A
2 x 10mm
2
+110vDC
32A
2 x 6mm
2
+220vDC
16A
2 x 2.5mm
2
18
– TSI Bravo – user manual – v7.0