There are 2 type of Wired Sensors 

– Normally Closed Type and Normally Open Type. 

They are respectively explained below: 

 Normally Closed Type           

            If more than one is to be connected in one Zone then they are connected in Series. Their contact points remain  
            Closed in ARMED condition. The contact gets Open when the sensor senses intrusion. 

 

            

Connect all the “Normally Closed Type Wired Sensors” in series and terminate on any of the “NC Type” Zone  

            wires of the Main Unit. 
             Any number of Wired Sensors can be connected as long as the total resistance of the Sensors and the wires is  
            less than 200 Ohms. 

 

 

Normally Open Type           

          If more than one is to be connected in one Zone then they are connected in parallel. Their contact points remain  
          

Open in ARMED condition. The contact gets closed when the sensor senses intrusion. Connect all the “Normally  

          Op

en Type Wired Sensors” in parallel and terminate on any of the “NO Type” Zone wires of the Main Unit. 

             

 

Note:

 

Each Zone can be connected to one or more Sensors provided they are same type i.e., They should  

           either be Normally Closed Type or Normally Open Type. However, different Zones can be used for different type  
          of Sensors. 

 

Wireless  Remote

 

&  Wireless  Sensors  should  be  registered  in  the  Main  Unit  as  described  under  the  heading 

“Wireless Sensors, Remotes & Panic Keys Registering/Deletion”.

 

 

.

   

                                                         Power On Procedure                                                            

.

 

After doing all the connections, remove the Main Unit from its wall bracket. 
Switch ON the 220V AC supply to the adapter. 
Now hang the main unit back on its wall bracket. 
The display show: 
                     

“Initialising GSM …..”   - In case of any error the display will show “Initialisation Error”    

                     

“Initialising BOARD ….”   

                   

 

.

                                                                           

Front Panel LED Indications                                                     

.

 

There are 2 LEDs on the front panel marked as ARMED and READY. 
ARMED LED glows in red color and READY in blue color. 
Following table illustrates the various conditions: 

LED 

Status 

Message 

ARMED 

OFF 

System is DISARMED 

 

ON 

System is ARMED 

 

Blinking 

System  is  in  Intrusion  mode  &  Tel  Number  (if 
entered) is being dialed by the system. 

Ready 

ON 

System is running on AC mains 

 

Blinking 

System is running on battery 

Low Battery indication                     

When the in-

built Batteries of the Main Unit get low, “Low Battery” appears in the display of the Main Unit. 

 

Sensor1 

Sensor 2 

 

Sensor 3

 

 
 

                 

Sensor 1              Sensor 2              Sensor 3

              

 
 

Connected to 

the “NC” 

Type Zone 

Wires & 

Black wire of 

20 Pin 

Connector 

Connected to 

the “NO” 

Type Zone 

Wires & 

Black Wire of 

10 Pin 

Connector  

Содержание BAS-G

Страница 1: ...Sounds control Auto Arm Disarm Time Holidays Battery Mode Power Switch Off in CMS Central Monitoring Station Date Time Setting Disarm Delay to ARM Panic Key Panic Key Silent Passwords Password Operat...

Страница 2: ...s for each day of the week User can also enter up to 10 Holidays in the system On those days the system continues in the previous day s status Example If the user has off days on Saturday and Sunday t...

Страница 3: ...level Passwords can only ARM or DISARM the system The History records would show which Password had ARMED DISARMED the system Remote Monitoring Whenever user wants or during Intrusion User can make a...

Страница 4: ...the systems dials out and plays the Siren sound message recorded by the user Optional the Wireless Sensor Number or the Wired Zone Number Refer Voice Message Recording for playing on Telephone calls...

Страница 5: ...wires are also provided with the system The wires from the female connectors are to be connected as per the tables given below 20 Pin Connector Wire Color To be connected to Red Adapter 12V DC Ve Outp...

Страница 6: ...However different Zones can be used for different type of Sensors Wireless Remote Wireless Sensors should be registered in the Main Unit as described under the heading Wireless Sensors Remotes Panic K...

Страница 7: ...in case of intrusion from wired sensor TYPE PAN PIR MS VBR Gas SMK or Misc in case of intrusion from wired sensor Remote in case Panic key is pressed from the Wireless Remote Keypad in case Panic key...

Страница 8: ...the Bypass zones get Armed To program a Zone as a Bypass Zone refer Wireless Sensor Operating Mode Wired Zones Operating Mode To ARM the system in Bypass mode Press Back Space and 7 together on the Ma...

Страница 9: ...0 1400 Quick Exit To ARM the system for the whole day enter ARM Time 0000 and DISARM time 2359 If all the 3 Time Groups of a day are OFF then the previous day s last status Armed Disarmed shall contin...

Страница 10: ...is connected to it The system has built in rechargeable Li batteries If longer back up is required then additional rechargeable 12V 7AH battery can be connected with an Optional Adapter having charger...

Страница 11: ...e programmed as MODE Always ARMED as explained under the heading Wired Sensor Operating Mode Operation Panic activation from the Remote Press PANIC Key Siren starts hooting and the system dials out on...

Страница 12: ...NG of the system with or without Master Password Press SET Enter Master Password 1234 Keep Pressing 2 to select Password Optn Press Press key UP or DOWN to select OFF or ON for this feature Press Quic...

Страница 13: ...or 4 minutes To extend the time dial 1 Another 4 minutes will be extended from the time of dialing 1 Press 2 to activate the siren Press 3 to de active the siren Press 4 to ARM the system Press 5 to D...

Страница 14: ...SIM installed in the BAS and get reply of the SIM balance SIMBAL CCCCC Where CCCCC The Code to check SIM balance given by the service provider Example In case of AIRTEL SIMBAL 123 Siren Hooting time...

Страница 15: ...orted pads represent 0 Note At least one of the pad should be shorted Default value 10111111 i e pad number 2 is shorted and all others are open So the programming in default case would be Enter Maste...

Страница 16: ...ding the range from one Signal Repeater to another Every Signal Repeater consumes one of the 75 Wireless Sensors capacity of the system SW and FSW do not work through Signal Repeaters Deletion This pr...

Страница 17: ...the balance in SIM of BAS 9 Add telephone number XXXX ATELjk ttttttttt j Tel location from 1 6 k E for SMS commands enable D for SMS commands disable tttttttt telephone number max 11 digits 10 Delete...

Страница 18: ...S G panel For all other programming press Settings choose the desired programming and enter your password to Confirm A confirmation SMS for the same will be received from the panel Wireless Sensor Typ...

Страница 19: ...ature is not available on that Telephone number If no Telephone number is entered the system cannot be ARMED Deleting a Telephone number Press Key 3 Enter Master Password 1234 Press UP or DOWN to sele...

Страница 20: ...se of Magnetic Sensor there will be another option to select MS Widout Swch or MS with Switch Press 1 for Widout Swch and 2 for MS with Switch Magnetic Sensor with switch is designed for applications...

Страница 21: ...ether the system is ARMED or DISARMED Silent Normal These Wireless Sensors will function in case of system being ARMED or BY Pass ARMED But there will be no siren sound Silent Always These Wireless Se...

Страница 22: ...ng false alarms caused due to short spikes in wiring Press SET Enter Master Password 1234 Keep Pressing 2 to select Wired Zn Delay Press Back Space Enter Time delay in milliseconds in 3 digits 010 750...

Страница 23: ...urglar Alarm System like any other commercial or residential alarm system does not guarantee protection against burglary fire or other emergency because of variety of reasons A properly installed and...

Страница 24: ...y dispute arising out of this warranty shall be subjected to jurisdiction of the arbitrator within the city of Delhi 15 The decision of Copper Connections Pvt Ltd on defects damages etc shall be final...

Отзывы: