4.4.2. Temperature sensor
The temperature sensor is connected to the unpluggable terminal block located directly on the mod-
ule. Pass its wire through the small cable gland provided.
Use a flat tipped screwdriver of a size adapted to the terminal block! (max.
2.5mm)
4.4.3. Filter pump
The filtering pump is connected under the first contactor (the left side one).
Check it is correctly tightened before powering on.
Use the earth bar at the bottom of the control box to connect it.