Enthalpy switch/receiver and Enthalpy sensor
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
66
For Differential Enthalpy Control
1
To mount the enthalpy sensor, insert 2 field-supplied 8 x 3/4-in. TEK screws through its side holes.
2
Repeat step 1 to mount the enthalpy switch/receiver.
3
On the switch/receiver, remove the 4 screws holding the cover on, then remove cover.
4
Set the
M1
to
M3
jumper to
M2
. Leave the other jumper on
Off
.
NOTE
The enthalpy sensor's jumpers should be left at their factory settings of
M3
and
Off
.
5
Replace the switch/receiver's cover and the 4 screws.
6
Wire the sensor to the switch/receiver. See figure below.
7
Connect the
GND
and
24 Vac
terminals on the enthalpy switch/receiver to the controller's power terminals.
8
Connect the
HI
or
LOW
terminals on the enthalpy switch/receiver to the controller's J2-6 input.