Primary Air Temperature sensor
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
41
Mounting location
Mount the sensor in the top or side of the supply duct.
Drill hole in top of duct
and let sensor hang down
Alternate location
inside of duct
Supply duct
To wire and mount the PAT sensor
1
Drill or punch a .5 inch (1.3 cm) hole in the duct.
2
Connect a .5 inch (1.3 cm) nominal field-supplied conduit between the zone controller enclosure and the
junction box.
3
Pass the sensor wires through the conduit.
4
Insert the sensor's probe into the hole.
5
Secure the sensor to the duct using the 2 mounting screws provided.
CAUTION
The tip of the sensor's 6-inch (15.2-cm) probe must not touch the inside of the duct.
6
Wire the sensor to the Open controller. See the controller's
Installation and Startup Guide
for details.